Controls; Ntegrated Ontrol; Oods; I Nstallation - Venmar 41502 Installation Manual

Avs units constructo 1.0 hrv and constructo 1.0 erv
Hide thumbs Also See for 41502:
Table of Contents

Advertisement

2.
INSTALLATION (
CONT
2.9
I
2 E
NSTALLING
XTERIOR
Choose an appropriate location to install the exterior hoods:
• There must be a minimum distance of 6' (1.8 m)
between the hoods to avoid cross-contamination
• There must be a minimum distance of 18" (457 mm)
from the ground
!
WARNING
Make sure the intake hood is at least 6 feet (1.8 m)
away from any of the following:
• Dryer exhaust, high efficiency furnace vent, central
vacuum vent
• Gas meter exhaust, gas barbecue-grill
• Any exhaust from a combustion source
• Garbage bin and any other source of contamination
Refer to figure at right for connecting insulated ducts to
the exterior hoods. An "Anti-gust intake hood" should be
installed in regions where a lot of snow is expected to fall.
3.

CONTROLS

3.1
I
C
NTEGRATED
ONTROL
All units are equipped with an integrated control, located under the unit, in front of the
electrical compartment. Use the push button (1) to control the unit. The LED (2) will then
shows on which mode the unit is in. Refer to table below.
LED C
OLOR
A
MBER
G
REEN
N
L
O
IGHT
If a problem occurs during the unit operation, its integrated control LED (2) will blink. The color of the blinking light depends on the type of
error detected. Refer to Section 9 T
3.1.1 B
OOT SEQUENCE
The unit boot sequence is similar to a personal computer boot sequence. Each time the unit is plugged after being unplugged, or
after a power failure, the unit will perform a 30-second booting sequence before starting to operate. During the booting sequence,
the integrated control LED will light GREEN or AMBER for 5 seconds, and then will shut off for 2 seconds. After that, the LED will
light RED for the rest of the booting sequence. During this RED light phase, the unit is checking and resetting the motorized damper
position. Once the motorized damper position completely set, the RED light turns off and the booting sequence is done.
NOTE: No command will be taken until the unit is fully booted.
'
)
D
H

OODS

R
ESULTS
U
L
NIT IS ON
OW
U
H
NIT IS ON
IGH
U
OFF
NIT IS
OR CONTROLLED BY A MAIN CONTROL
on page 17 for further details.
ROUBLESHOOTING
E
XHAUST HOOD
I
NTAKE HOOD
18"
(457
)
MM
6'
(1.8
)
M
VD0028
S
PEED
S
PEED
10
6" Ø
(152
)
MM
O
PTIONAL DUCT
LOCATION
18"
(457
)
MM
T
APE AND DUCT TIE
WARNING
AVERTISSEMENT
Risk of electric shock. Before performing
Danger d'électrocution. Débranchez
any maintenance or servicing, always
toujours l'appareil avant d'entreprendre
disconnect the unit from its power source.
des travaux d'entretien ou de réparation.
CAUTION
ATTENTION
Unscrew both screws to open the electrical
Dévisser les deux vis pour ouvrir le compartiment
compartment. To completely remove, detach
électrique. Pour retirer complètement, le
from its retention wire inside.
détacher de son fil de rétention intérieur.
No light
OFF or remote controled
Amber light
LOW speed
Green ligh
HIGH speed
Blinking light
See User Manual
Sans lumière
Arrêté ou contrôlé
par contrôle mural
Lumière ambre
Basse vitesse
Lumière verte
Haute vitesse
Clignotant
Voir guide d'utilisation
1 2
VD0182
6'
(1.8
)
M
18"
(457
)
MM