Real Time Clock; Access Control; Power-On Sequence - ABB REF601 Applications Manual

Feeder protection and control feeder protection
Hide thumbs Also See for REF601:
Table of Contents

Advertisement

1MDU07212-YN Rev. C
2.4.4
2.4.5
2.4.6
REF601 / REJ601
Application Manual
Sr.
Event type
Description
No.
32
Start
An event for general start will be capture for
both rising and falling which will be from any
of start of I>,I>>, I>>> ,Io> ,Io>>, I2>, I2/I1>
33
Trip
an event for general trip will be capture for
both rising and falling which will be from any
of trip of I>,I>>, I>>> ,Io> ,Io>>, I2>, I2/I1>
and Thermal trip
34
Factory default
event for factory default

Real Time Clock

IED comes with a real time clock with user settable date and time. Date can be set
in "DD/MM/YY" format and time can be set in "HH:MM:SEC" format. The time
stamping have 1 ms resolution. RTC is used for time stamping the event logs and
as well as fault records . In case of power failure RTC will have a stored energy
backup for around 48 hrs. at ambient temperature when stored energy element is
fully charged. Initial time setting is "01/01/2011" and "00:00:00:000".

Access Control

To protect the relay from unauthorized access and to maintain the integrity of
information, the relay is armed with a three level, role-based user authentication
system with individual password for the operator, engineer (Setting level) and
administrator level. With the Ver. 2.2 FP1 REF601/REJ601 supports two modes
for password handling:
1. a combination of different navigation keys (default mode)
2. alphanumeric password

Power-ON sequence

The Power-ON sequence takes around 6 sec.
In case the optional communication on MODBUS RTU / IEC 60870-5-103 is
present, the startup time takes around 40 sec.
Section 2
REF601/REJ601 overview
Data considered
Start ↑
Start ↓
Trip ↑
Trip ↓
Factory Default
15