ABB REF601 Applications Manual page 31

Feeder protection and control feeder protection
Hide thumbs Also See for REF601:
Table of Contents

Advertisement

1MDU07212-YN Rev. C
4.8.2.1
4.8.2.2
4.8.2.3
REF601 / REJ601
Application Manual
Setting range for Auto-reclose function
Table 13
Setting ranges for Auto-reclose function I <-> O, 79
Parameter
Description
O→I start mode
Auto reclose initialization mode
CB ready
Type of CB ready signal
available
# of cycle
Number of Auto reclose cycles
(0 = Auto-reclose not in use)
Activate t
Time between General Start
and General Trip for activation
of O→I in Mode 2
Pulse tp
Auto reclose pulse time
Cycle t1
Dead time for first auto reclose
cycle
Cycle t2
Dead time for second auto
reclose cycle
Cycle t3
Dead time for third auto
reclose cycle
Cycle t4
Dead time for fourth auto
reclose cycle
Reclaim tr
Reclaim time
Block tb
Auto reclosure block time.
Configurable inputs to Auto-reclose function
Table 14
Configurable inputs to Auto-reclose function I <-> O, 79
Name
Type
CB CLOS POS
BOOL
EXT TRIP
BOOL
CB READY
BOOL
Configurable outputs of Auto-reclose function
Table 15
Configurable Outputs to Auto-reclose function I <-> O, 79
Name
Type
O→I CLOSE
BOOL
O→I IN
BOOL
PROGRESS
FINAL TRIP
BOOL
O→I BLOCKED
BOOL
Protection and Control Function
Range
Unit
1 = Select Trip
2 = Gen Start &
Trip
1 = OCO
2 = CO
0 ... 4
0.1 ... 5
s
0.2 ... 20.0 [s]
s
0.20 ... 300.00 [s]
s
0.20 ... 300.00
s
0.20 ... 300.00
s
0.20 ... 300.00
s
1 ... 300
s
1 ... 300
s
Description
Circuit breaker closed position information
External trip input
Circuit breaker ready information
Description
Closing command from auto reclosure
Reclosing cycle in progress, activated during
reclose time
Final trip from auto reclosure
Auto reclosure blocked
Section 4
Step
Default
1
1
1
1
1
1
0.1
0.8
0.1
0.2
0.01
0.5
0.01
0.5
0.01
0.5
0.01
0.5
1
1
1
5
25