ABB REF601 Applications Manual page 36

Feeder protection and control feeder protection
Hide thumbs Also See for REF601:
Table of Contents

Advertisement

Section 4
Protection and Control Function
4.9.2.1
4.9.2.2
4.9.2.3
30
Setting range for thermal overload protection
Table 16
Setting range for thermal overload protection 3Ith, 49
Parameter
Description
Mode ϑ
Mode of thermal overload
protection*
ϑ
Initial thermal level of the
0
apparatus
I
Reference current leading to
b
thermal calculation
τ
Heating time constant of
machine
τ
Cooling time constant of static
↓s
machine
τ
Cooling time constant of
↓r
rotating machine*
ϑ
Alarm value
alm
ϑ
Operate value
trip
ϑ
Start inhibit value
startinhibit
ϑ
Percentage by which
EM
will be increased in emergency
mode
Mode ϑ
Options for calculating thermal
powerOFF
value during power interruption
*Setting in REF601 and REJ601 hidden (fixed set to static mode)
Configurable inputs to thermal overload protection
Table 17
Configurable inputs to thermal overload protection 3Ith, 49
Name
Type
RESET
BOOL
BLOCK
BOOL
Configurable outputs of thermal overload protection
Table 18
Configurable inputs to thermal overload protection 3Ith, 49
Name
Type
ALARM
BOOL
OPERATE
BOOL
Θ
REAL
Range
0 = rotating
1 = static
0...100
0.1 ... 1.5
1 ... 300
1 ... 300
1 ... 1000
50 ... 200
50 ... 200
50 ... 200
j
10... 100
trip
1...4
Description
Description
Alarm
Operate
Value of thermal image
1MDU07212-YN Rev. C
Unit
Step
Default
-
1
0
%
1
80
xIn
0.1
1.0
min
1
45
min
1
45
min
1
180
%
1
121
%
1
144
%
1
105
%
1
50
-
1
4
REF601 / REJ601