4.3

7406RC Board Assembly Overview

DS1 - DS2 : standard ex works (Standardeinstellung ab Werk)

4.3.1 Line Voltage and Monitoring Device Configuration

The lines of RC Function Board 7406RC can be operated with various voltages. For this
purpose, jumpers 8-13 (see imprint) must be pre-set for voltage monitoring.
Jumper setting
Line 1
J13
J12
J11
12 / 27
hopf
Elektronik GmbH
Nottebohmstr. 41 • D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: info@hopf.com
7406RC D
ESIGN
J11
60V
J12
48V
J13
24V
J8
60V
J9
48V
J1
J4
J10
24V
J5
X2
J2
1
J14
Description
Function
ST3
Service connector
X2
Diagnosis connector
Service jumper
J14, J6
MB3, J1
Operating voltage measuring points (5 V DC)
J8, J9, J10
Voltage monitoring setting for line 1
J11, J12, J13
Voltage monitoring setting for line 2
J2, J3
Diagnosis jumper line 1
J4, J5
Diagnosis jumper line 2
Line voltage
Line 2
J10
J9
J8
DS2
on
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Monitoring voltage
Line fault on insufficient voltage
24 V
48 V
60 V
7406RC Slave Clock Control Board for System 7001RC - V02.03
DS1
on
MB3
ST3
1
J6
18 V
36 V
45 V