Change transmission speed
It changes the transmission speed after it returns the response.
・Command from master; Control code 17H
68H
A0
A1
A2
Transmission address
・Response from slave (normal)
68H
A0
A1
A2
Transmission address
Change password
It changes password.
It is available only with pressing <MODE> key (programming key).
Without pressing programming key, it doesn't response.
For changing password, authorization level (PA0) should be designated, but only '0' is supported.
・Command from master; Control code 18H
68H
A0
A1
Transmission address
DI0
34 3F 33 37
Continue
(Add 33H to 01 0C 00 04)
(Only "0" is supported.)
continue
・Response from slave (normal)
68H
A0
A1
A2
Transmission address
A3
A4
A5
68H
Transmission speed
(bit flag)
A3
A4
A5
68H
A2
A3
A4
DI1
DI2
DI3
Designate authorization
Authorization level for password
to change (33H fix)
A3
A4
A5
PAn
Authorization level for changed
password (33H fix)
17H
01H
Control code
bit
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
97H
01H
A5
68H
Control code
PA
level (33H fix)
PAn
68H
18H
04H
P0n
Changed password
61
KW9M Eco-POWER METER
Z
Transmission speed
(bit flag)
Transmission speed [bps]
38400
19200
9600
4800
2400
1200
空き
空き
Z
Transmission speed
(bit flag)
18H
0CH
P0
P1
P2
Designate the present
password (P2: 33H fix)
P0n
P1n
P2n
New password