Wrong Installation; Correct Installation; Venting; Deflector Area - Beko Bekomat 14 Instructions For Installation And Operation Manual

Condensate drain
Table of Contents

Advertisement

Installation • Instalación
Installation • Instalação
wrong • no correcto
incorrect • incorrecto
18
correct • correcto
correct • correcto
english
1. Feed pipe and fitting at least ¾"!
(internal dia > 0,71 inch)
2. No filters in feed line
3. Slope in feed line > 1%!
4. Only use ball valves with full open
port!
5. Pressure: min. 12 psig or 18 psig!
(check type plate for correct pres-
sure)
6. Short pressure hose!
7. For each yard of rising slope in the
outlet line, the required minimum pres-
sure will increase by 1.5 psig.
The rise of the outlet line must not
exceed 17 feet!
8. Collecting line min. 1'' with 1% slope
9. In the case of inflow problems, install
venting line.
Note:
Pressure differences!
Each condensate source must be drained
separately!
Note:

Venting!

If the feed line cannot be laid with suffici-
ent slope, it will be necessary to install a
venting line!
Note:

Deflector area!

If drainage is to take place directly from a
line, it is advisable to arrange the piping
so that the air flow is diverted.
BEKOMAT 14, 14 CO, 14 CO PN25