Contact Current - Testboy TV 470 Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

Contact current

A measurement is allowed for devices with protection class-II that have ex-
posed conductive components when there are concerns with a measure-
ment of the insulation resistance or when an interruption in usage is not pos-
sible. This also applies for measurements of protection class-I devices that
have exposed conductive components and do not have a connection to the
PE conductor.
Limit
DIN VDE 0701-0702:2008-6
< 0.5 mA
Low protection voltage
Values above the following specifications should be viewed as actively dan-
gerous under normal circumstances.
Limit
EN 61010-1:2011-07
33 V AC / 70V DC
®
Testboy
TV 470
Information to DIN VDE 0701-0702:2008-06
67

Advertisement

Table of Contents
loading

Table of Contents