RUGGEDCOM RMC
Installation Guide
Test
IEC 61000-4-17
IEC 60255-5
a
Siemens specified severity level.
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RMC meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
IEEE Test
C37.90.3
C37.90.2
C37.90.1
C37.90
Environmental Type Tests
Test
IEC 60068-2-1
EMI and Environmental Type Tests
Description
Ripple on DC Power Supply
Dielectric Strength
HV Impulse
IEEE 1613
Clause
9
ESD
8
Radiated RFI
7
Fast Transient
Oscillatory
6
HV Impulse
Dielectric
Strength
Description
Cold Temperature
DC Power ports
Signal ports
2 kVAC (Fail-Safe Relay output)
DC Power ports
AC Power ports
Signal ports
5 kV (Fail-Safe Relay Output)
DC Power ports
AC Power ports
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Test Ad
-40 °C (-40 °F), 16 Hours
Test Levels
10%
1.5 kVDC
2 kVDC
5 kV
5 kV
Test Levels
+/- 2 kV, +/- 4 kV, +/- 8 kV
+/- 4 kV, +/- 8 kV, +/- 15 kV
35 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
2.5 kV common mode @ 1MHz
2.5 kV common, 1 kV
differential mode @ 1MHz
2.5 kV common, 1 kV
differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kVAC
1.5 kVDC
2 kVAC
Test Levels
Severity Levels
Chapter 6
Certification
Severity Levels
3
21