Connecting To Gas Supply; Installation Requirements; Installation Items Needed - Paloform BENTO 42 Installation And Owner's Manual

Concrete
Table of Contents

Advertisement

CONNECTING TO GAS SUPPLY

WARNING:
A qualified service person must connect
the appliance to the gas supply. Follow all
local codes.
CAUTION:
Use only new black iron or steel pipe.
Internally tinned copper tubing may be
used in certain areas. Use pipe of 1/2"
diameter or greater to allow proper gas
volume to Outdoor Fire Pit Burner. If pipe
is too small, undue loss of pressure will
occur.

INSTALLATION ITEMS NEEDED:

Before installing the Outdoor
Fire Pit, make sure you have all items
listed bellow:
piping (check local codes)
sealant
manual shutoff valve
adjustable (crescent) wrench or pliers
sediment trap
tee joints
pipe wrench

INSTALLATION REQUIREMENTS

Installation must include a manual shutoff valve, union,
and plugged 1/8" NPT tap. Locate NPT tap within reach
for test gauge hook up. NPT tap must be upstream from
the appliance.
Apply pipe joint sealant lightly to male threads. This will
prevent excess sealant from going into pipe. Excess
sealant in pipe could result in a clogged burner injector.
Install sediment trap in supply line as shown below.
Locate sediment trap where it is within reach for cleaning
and trapped matter is not likely to freeze.
A sediment trap prevents moisture and contaminants
from entering the Outdoor Fire Pit controls. If a sediment
trap is not installed, or is installed incorrectly, the unit may
not work properly.
APPROVED FLEXIBLE GAS HOSE
A.G.A DESIGN-CERTIFIED MANUAL
SHUTOFF VALVE WITH 1/8" NPT TAP
3" MINIMUM
BENTO 42 CONCRETE FIRE PIT Match-lit | Installation & Owner's Manual
CHECKING GAS CONNECTION
for leaks after installing or servicing. Correct all leaks
immediately.
a leak. Apply a mixture of liquid soap and water to all
joints. Bubbles forming on joints while the gas is running
indicate a leak. Correct all leaks at immediately.
Test Pressures in Excess Of 1/2 psi (3.5 kPa)
This appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of ½ psi (3.5 kPa).
Test Pressures Equal To or Less Than 1/2 psi (3.5 kPa)
This appliance must be isolated from the gas supply
piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than ½ psi (3.5
kPa).
FROM GAS METER (5" W.C.
TO 10.5" W.C. PRESSURE)
CAP
PIPE NIPPLE TEE JOINT
SEDIMENT TRAP
WARNING: Test all gas piping and connections
WARNING: Never use an open flame to check for
8