(2) Outdoor unit

Model SCM45ZD-S
Item
Cooling capacity
Heating capacity
Power source
Power consumption
Running current
Noise level
Exterior dimensions
Height × Width × Depth
Color
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Refrigerant control
Refrigerant
Refrigerant oil
Air handling equipment
Fan type & Q'ty
Motor
Air flow (at high)
Shock & vibration absorber
Safety equipment
Size × Core × Number
Refrigerant
Connecting method
piping
Attached length piping
Insulation
Power source supply
Size × Core number
Connec-
tion wiring
Connecting method
Accessories (included)
Indoor units to be combined
Notes (1) The data are measured at the following conditions.
Operation
Cooling
Heating
(2) The values for capacity and power consumption shown in a range ( ) indicate the minimum and maximum of the range.
(3) If the piping length exceeds 20 m, additional charging is required. (20g/m)
Model
W
W
Cooling
W
Heating
Cooling
A
Heating
Sound level
dB
Power level
mm
kg
kW
kg
R
W
CMM
mm (in)
Item
Indoor air temperature
DB
27ºC
20ºC
SCM45ZD-S
4500 (700 ~ 5600)
5600 (700 ~ 6800)
1 Phase 220/230/240V 50Hz
1390 (200 ~ 2160)
1540 (200 ~ 2340)
6.4/6.1/5.9
7.1/6.8/6.5
Cooling : 45/45/47
Cooling : 60/60/62
640 × 850 × 290
Stucco white
5CS102XFD [Scroll] × 1
Direct start
Capillary tubes + Electric expansion valve
R410A 1.6 (Pre-charged up to the piping length of 20m)
0.48 (RB68A)
Propeller fan × 1
Rubber (for compressor)
Compressor overheat protection, Overcurrent protection
Serial signal error protection
Liquid line: φ 6.35 (1/4") × 2
Gas line: φ 9.52 (3/8") × 2
Flare connecting
Necessary (Both Liquid & Gas lines)
Terminal block (Screw fixing type)
× 4 cores (Including earth cable) × 2
1.5 mm
2
Terminal block (Screw fixing type)
Installation sheet, Manual instruction
SKM22, 25, 28, 35 type,
STM25, 35 type,
SRRM25, 35 type
Outdoor air temperature
WB
DB
19ºC
35ºC
7ºC
6
-
-
Heating : 47/47/49
Heating : 62/62/64
44
0.7
35
40
WB
24ºC
ISO-T1, JIS C9612
6ºC
ISO-T1, JIS C9612
Standards