5.2.3 Guidelines for the Timing of Compressor Overhaul
The compressor overhaul interval is largely affected by the compressor operating conditions, type and
status of refrigerant and oil, and the system/equipment in which the compressor is operated.
The table below shows the recommended interval of overhaul, as a guideline.
Table 5-4 Guidelines for the Timing of Overhaul Based on the Conditions of Use
Category of operating condition
Relatively stable operating condition
Relatively variable operating condition
Frequently started/stopped, and
relatively variable operating conditions
Note 1: The above guidelines are only applicable when the compressor is operated within the operation
limits specified separately.
(Refer to Section 2.3.2 "Operation Limits" in this manual.)
Note 2: The above guidelines are only applicable when the compressor undergoes daily and periodical
inspections specified separately.
(Refer to Section 5.2.1 "Daily Management" in this manual.)
Note 3: Inspect the compressor at the intervals of specified period or operating hours, whichever comes
first.
Note 4: The above guidelines do not constitute any warranty.
Compound 2-stage Screw Compressor
1612LSC Speed Increaser Type
(standard package)
Application
Guideline for the overhaul timing
example
Cold storage and
Every 5 years or 40,000 operating hours
refrigeration
Ice maker/chiller
Every 4 years or 30,000 operating hours
Heat pump
Every 3 years or 20,000 operating hours
5-6
2202L5JE-DA-C5-N_2015.05.
5 Maintenance and Inspection
5.2 Maintenance and Inspection List