Compressor Assembly; Storage And Transport; Setting Up; Pipe Connections - GEA HGX6 R134a series Assembly Instruction Manual

Bock compressor
Table of Contents

Advertisement

4| Compressor assembly

4.1 Storage and transport

?
Fig. 5
Fig. 6

4.2 Setting up

D
GB
F
3
E
Fig. 7
Fig. 8
Fig. 9

4.3 Pipe connections

10
INFO!
New compressors are factory-filled with inert gas (3 bar nitrogen).
Leave this service charge in the compressor for as long as possible
and prevent the ingress of air.
Check the compressor for transport damage before starting any
work.
Storage at (-30°C) - (+70°C), maximum permissible relative humidity
10% - 95%, no condensation
Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
Use transport eyelet.
Do not lift manually!
Use lifting gear!
ATTENTION! Attachments (e.g. pipe holders, additional units, fastening parts,
etc.) directly to the compressor are not permissible!
2
Provide adequate clearance for maintenance work.
Ensure adequate compressor ventilation.
Do not use in a corrosive, dusty, damp atmosphere or a
combustible environment.
Setup on an even surface or frame with sufficient load-
bearing capacity.
Single compressor preferably on vibration damper.
Duplex and parallel circuits always rigid.
ATTENTION! Superheating can damage the valve.
Remove the pipe supports from the valve for soldering.
Only solder using inert gas to inhibit oxidation products (scale).
1
F
E
D
C