Properties
1.1 Digital electronic module 2DO DC24V/2A HF (6ES7132-4BB31-0AB0)
Rated load voltage L+ (from the power module)
•
Total current of the outputs (per module)
Electrical isolation
•
•
Permissible potential difference
•
Insulation tested
Current consumption
•
Power dissipation of the module
Status display
Diagnostics function
•
•
Output voltage
•
Output current
•
•
Output delay (for resistive load)
•
•
Load resistor range
Lamp load
Connecting two outputs in parallel
•
•
Control of a digital input
Switch rate
•
•
•
Limitation (internal) of the voltage induced on
circuit interruption
Reverse-voltage proof
Short-circuit protection of the output
•
Polarity reversal can lead to the digital outputs being connected through.
1
Per channel
2
10
Polarity reversal
Between the channels
Between the channels and backplane bus
Between the different circuits
From the rated load voltage L+ (no load)
Group error
Diagnostics functions readable
At signal "1"
At signal "1"
–
Rated value
–
Permitted range
With signal "0" (leakage current)
At "0" to "1"
At "1" to "0"
For redundant triggering of a load
To increase performance
For resistive load
On inductive load
For lamp load
Threshold on
Voltages, currents, potentials
24 VDC
Yes
1
4 A
No
Yes
75 VDC / 60 VAC
500 VDC
Max. 5 mA per channel
Typically 1.4 W
Status, interrupts, diagnostics
Green LED per channel
Red "SF" LED
Yes
Data for selecting an actuator
Min. L+ (-1 V)
2 A
7 mA to 2.4 A
Max. 0.5 mA
Max. 100 µs
Max. 400 µs
12 Ω to 3.4 kΩ
Max. 5 W
Yes (per module)
No
Yes
100 Hz
2 Hz (0.5 H)
10 Hz
Typically L+ (-55 V to -60 V)
Yes, if using the same load voltage as at the
power module
Yes
2
Typically 4 A
Digital electronic module 2DO DC24V/2A HF (6ES7132-4BB31-0AB0)
Manual, 04/2007, A5E01077255-01