Parameters
2.1
Parameters
This table shows the parameters for digital output modules:
Table 2-1
Parameters for digital output modules
2DO 24 VDC/2 A HF
Response to CPU/master STOP
Substitute value
1
Diagnostics: Wire break
Diagnostics: Short circuit to M
If the interface module or COMPACT module becomes deenergized, the digital output modules will not produce
1
substitute values. Output value = 0.
A wire break is only detected in the switched output state.
2
Digital electronic module 2DO DC24V/2A HF (6ES7132-4BB31-0AB0)
Manual, 04/2007, A5E01077255-01
Range of values
Substitute a value
•
Keep last value
•
"0"
•
"1"
•
Disable
•
2
Enable
•
Disable
•
Enable
•
Default setting
Substitute a value
"0"
Disable
Disable
2
Applicability
Module
Channel
Channel
Channel
11