Performance Specifications - Panasonic FP0 Series Specifications

Fp0 series programmable controller
Hide thumbs Also See for FP0 Series:
Table of Contents

Advertisement

FP0 S-LINK Unit
Connects directly to the S-LINK for reduced wiring
S-Link is a system which simplifies connection of rapidly increasing control devices accompanying
progressing automation and is useful in reducing your costs and construction time.
Features
1. Small size of only W30 x H90 x D60 mm.
2. Controls 64 input points and 64 output points.
3. Allows simultaneous use of expansion units.
FP0-SL1
4. A wide range of I/O modules allow manifold customer-oriented network layouts.
Power Supply Specification
Item
Power supply
24VDC

Performance Specifications

Item
S-LINK block: 64 input points,
Number of I/O points
64 output points (fixed)
Max. 3 units
Expansion
Expansion section:
Max. 96 points
Operation speed
0.9µs/step
Internal memory
EEPROM
Memory capacity
5k steps
1,008 points
Memory Internal relay
of
Timer/Counter
144 points in total
execution Data register
6,144 words
Applicable Functions
Item
Pulse catch/Interrupt input
None
Analogue I/O
Available by adding analogue I/O unit
Volume input
None
High-speed Counter
None
Pulse output
None
1 ch is equipped.
RS232C port
3P terminal blocks (made by
Phoenix Contact Co.)
Direct connection for reduced wiring
The layout of devices becomes flexible
FP0
S-LINK Control unit
and the design is easier due to the
W30
H90
D60
'T'-branch multi-drop wiring.
Maximum length: 200m
Max. 128 points
T-branch multi
drop wiring
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Makes use of the T-shaped connectability of the S-LINK for reduced wiring and reduced size
of the control panel.
Able to control up to 128 points for S-LINK-related devices.
Similar to other FP0 units, up to three expansion units can be used for efficient I/O wiring.
Description
Description
Description
2 signal wires
2 power
supply wires
Applicable Network
Item
Control unit functions as S-LINK
master station.
Remote I/O
Available as a slave station of
MEWNET-F by adding I/O link unit
Inter-PLC link
Not available
Linkable with tool port or
Computer link
RS232C port
Available, Type with RS232C
Modem connection
port can also send data
Other Built-in Functions
Item
Program block-edit
Available
during RUN
Constant scan
Available
Adjustable input time
Not available
filtering
Clock/Calendar function
None
Wire-saving
The use of wires is greatly reduced and the number of connecting
terminal blocks is minimized, resulting in large reduction in cost, as
well as, the waste generated during wiring.
Space effective
S-Link devices are compact. The control box can be mounted in a
tight space.
Quick construction
Sensors cab be easily connected with plug-in connection.