Setting ds2 and ds1 for parallel operation
Master
DS-8 not used
DS-7 not used
DS-6 not used
DS-5 AES
na
DS-4 Inv. voltage Set
DS-3 Inv. freq
Set
DS-2 Master
DS-1 Master
To store the settings after the required values have been set: press the 'Up' button of
the master for 2 seconds (upper button to the right of the DIP switches, see appendix
A, position J). The overload and low-battery LEDs will flash to indicate
acceptance of the settings.
You can leave the DIP switches in the selected positions, so that the settings can
always be recovered.
Setting ds2 and ds1 for 3-phase operation
Leader (L1)
DS-8 not used
DS-7 not used
DS-6 not used
DS-5 AES
na
DS-4 Inv. voltage Set
DS-3 Inv. freq
Set
DS-2 Leader
DS-1 Leader
As the table above shows, the Inverter voltage should be set separately (ds4) for
every Inverter
AES can be used on stand alone units only.
To store the settings after the required values have been set: press the 'Up' button of
the Leader for 2 seconds (upper button to the right of the DIP switches, see appendix
A, position J). The overload and low-battery LEDs will flash to indicate
acceptance of the settings.
You can leave the DIP switches in the selected positions, so that the settings can
always be recovered.
To start the system: first, turn all devices off. The system will start up as soon
as all devices have been turned on.
off
DS-8 not used
off
DS-7 not used
off
DS-6 not used
x
DS-5 na
DS-4 na
DS-3 na
off
DS-2 Slave 1
on
DS-1 Slave 1
Follower (L2)
off
DS-8 not used
off
DS-7 not used
off
DS-6 not used
x
DS-5 na
DS-4 Set
DS-3 na
on
DS-2 L2
off
DS-1 L2
Slave 1
off
off
off
x
x
x
off
off
off
off
off
x
x
off
off
Slave 2 (optional)
DS-8 not used
DS-7 not used
DS-6 not used
DS-5 na
x
DS-4 na
x
DS-3 na
x
DS-2 Slave 2
DS-1 Slave 2
on
Follower (L3)
DS-8 not used
DS-7 not used
DS-6 not used
DS-5 na
x
DS-4 Set
DS-3 na
x
DS-2 L3
DS-1 L3
on
off
off
off
off
off
off
off
off