Advertisement

5. Check the main field for a grounded condition by
using a megohmmeter. Apply 500 volts DC to
either field lead and the main field frame. Follow
the
instructions
manufacturer when performing this test.
Figure 7-12.
A
500 kOhms (1/2 megohm) and higher indicates the
main field is good.
approximately
500
deterioration of the winding insulation and possible
current flow to ground. Repair or replace the main
field.
7
AC
AC
AC
6
5
1. Main field (rotor)
2. Stator windings
3. Rectifier module
4. Shaft connection
Figure 7-12 Megohmmeter Connections on Main
Field

7.9 Stator

The stator consists of a series of coils of wire laid in a
laminated steel frame. The stator leads supply voltage
to the AC load and exciter regulator.
Leads 1, 2, 3, and 4 are the generator output leads.
Leads 33, 44, and 55 are the voltage regulator supply
and sensing leads. The output of leads B1 and B2 are
rectified by BR1 to supply the control voltage. BR1 is
located on the controller circuit board.
Prior to testing, inspect the stator for heat discoloration
and visible damage to the housing lead wires or
exposed and varnished areas of the frame laminations.
Be sure the stator is securely fastened in the stator
housing.
The stator produces electrical output (AC) as the
magnetized main field rotates within the stator windings.
Test the condition of the stator according to the following
procedure. Refer to the schematic in Figure 7-13 when
performing the following tests.
TP-6053 7/04
of
the
megohmmeter's
reading
of
approximately
A reading of less than
kOhms
indicates
1
F+
F--
3
2
4
5588712
5. Megohmmeter
6. Armature
7. Exciter field
Stator Test Procedure
1. Check the generator output lead connections. See
Section 10, Voltage Reconnection and Wiring
Diagrams.
See
2. Disconnect all the stator leads to isolate the
windings. To check the stator continuity, set the
ohmmeter on the R x 1 scale. Contact the red and
the
black ohmmeter leads; adjust the ohmmeter to
zero ohms.
connecting the meter leads to the stator leads as
shown in Figure 7-13. Perform the stator tests on
all the stator windings. See Figure 7-14.
3. Contact the ohmmeter leads and readjust the
ohmmeter to zero ohms.
resistance of the stator windings by connecting the
meter leads to the stator leads 1 and 2, 3 and 4,
B1 and B2, etc. See Section 1, Specifications, for
the stator resistance values. Replace the stator if
readings do not fall within the specified value.
Note: The stator resistance will vary directly with
increased temperature.
F1
F2
6
5
1. Main field (rotor)
2. Stator windings
3. Rectifier module
Figure 7-13 Stator Ohmmeter Connections
Between Leads
1 and 3, 4, 33, 44, 55
1 and 55, B1, and B2
4 and B1 and B2
55 and B1 and B2
Any stator lead and ground
Figure 7-14 Stator Continuity
Check the stator continuity by
Check the cold
33
55
1
F+
AC
AC
AC
F--
3
B1
B2
4
4. Ohmmeter
5. Armature
6. Exciter field
1 and 2
3 and 4
33 and 44
33 and 55
B1 and B2
Section 7 Generator Troubleshooting
3
4
44
1
2
2
5588713
Continuity
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
39