Status Codes - Class - Fronius 3.0-3-S Operating Instructions Manual

Grid-connected inverter
Hide thumbs Also See for 3.0-3-S:
Table of Contents

Advertisement

Available languages

Available languages

Code
Description
301
Overcurrent (AC)
302
Overcurrent (DC)
303
DC module overtemperature
304
AC module overtemperature
305
No power being fed in, despite closed
relay
PV output too low for feeding energy
306
into the grid
DC low
307
DC input voltage too low for feeding
energy into the grid
IMPORTANT! Due to the low level of insolation early in the morning and in the evening, the status codes 306
(Power low) and 307 (DC low) are displayed routinely at these times of day. These status codes do not indicate
any kind of fault.
308
Intermediate circuit voltage too high
309
DC input voltage MPPT 1 too high
311
Polarity of DC strings reversed
313
DC input voltage MPPT2 too high
314
Current sensor calibration timeout
315
AC current sensor error
316
InterruptCheck fail
325
Overtemperature in the connection
area
326
Fan 1 error
327
Fan 2 error
*) If the status code is displayed all the time: notify a Fronius-trained service engineer
**) Fault is rectified automatically. If this status code keeps recurring, contact your system
engineer
Status codes –
Some of the class 4 status codes necessitate intervention by a Fronius-trained service
Class 4
technician.
Code
Description
401
Unable to communicate with the power
stage set
406
AC module temperature sensor faulty
(L1)
407
AC module temperature sensor faulty
(L2)
408
DC component measured in the grid too
high
46
Behaviour
Short-term interruption while
feeding energy into the grid.
The inverter resumes its start-
up routine.
Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.
Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.
Short-term interruption while
feeding energy into the grid
The inverter resumes its start-
up routine.
Short-term interruption while
feeding energy into the grid
The inverter resumes its start-
up routine.
Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.
Behaviour
The inverter will automati-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid
Remedy
*)
Purge cooling air open-
ings and heat sink; **)
**)
wait for sufficient level of
insolation;
**)
**)
*)
Remedy
*)