Mitsubishi MELSEC F2-60MR Instruction Manual page 13

Table of Contents

Advertisement

I
Connect external load devices e.g. contactors, pilot lamps, sotenoid (electromagnetic)
valves, etc.,
to output terminations of the base unit and extension unit (if used).
As shown in the above figure, common terminals are provided
for the output terminations.
As these commons are not linked and cover each four output terminals in their block, different
types of power can be used
as
shown in the above example
as
far
as
the output terminals in
a
block share one type
of
power.
The load limitation of the triac (SSR) outputs
is 1A
for each individual output, but the total
collective output load should no exceed 8A across
all 16
outputs
at
AC 110/120V or AC 220/
24OV.
For inductance loads, the rated coil of magnetic contactors sl-tould be within 50VA
a t
AC 110/
be required. For lamp loads above IOOW, an external relay will atso be required.
Each triac (SSR) inside the
unit
will withstand moderate surge currents, and is protqcted bv
a
residual current circuit. With the triac
'off'
current leakage is
less
than 1.2mA
a t
AC 120V or
2.2mA
a t
AC 220V. However,
it is
possible that this might have some effect on external loads.
It is
not possible to operate triac output card
on
DC toads.
12OV or 100VA
a t
AC 220/240V. If the coil toad
is
over these limits, then an externa1)relay will
4-3
TRANSfSTOR OUTPUT MODELS (F2-40/60CIT,
-17)
SINK OUTPUT TYPE
1
DC24V 0 14301 431 /4321433143414351436f437[53015311532[5331534i 535[536[5371
DC24V
0
I
d
2A t
P
b
4
DC24VO 31 33 3 5 37
431 433 435 437
531 533 535 537 DC24VO
40 42 44 46
440 442 444 446
540 542 544 546
DC24VO
41
43 45
47
441 443 445 447
541 543 545 547
DC24V @