SWITCH 4. KEYPAD SOUNDER
Enables or disables the keypad sounder. In the OFF ~sfklonthe
keypad sounder will beaotlve.
In the ON postion the keypad will only sound indicating the depression of keys.
NOTE: For U,L. aDDlicationsthe kewad sounder MUST be enabled,
This switch Is only read upon exh from ths ksypad programming
sequence.
Therefore to change the keypad eounder wtus
set the switch (SW4) to the
desired posltlon then enter and exft from the ksypad programming
mode,
4.6.
AUXILIARYPOWR
AuxiHaryWwer(13.8VDC
regulated) can be obtained from three different outputs of the XL4
panel. Thetotal regulated output Wwerfmmthe
XL-4is9OOmA
(800mAfor ULapplicafions) wifh
the following current distribution;
TERMINALS
MAX. CURRENT
APPLICATION
13 (+)& 16(-)
280 W. (250 mA UL)
Keypads
17 (+)& 16(-)
470 MA. (250 mA UL)
Mist (Passives etc.).
or 35 (+) &34 fi)
33 (+)& 32(-)
150 mA. (100 mA UL)
Smoke Detectors
NOTE: Terminal 35(+) is internally connected to t 7 (+). The maximum current avsilable from both
of these points added together is 470 MA (250 mA for UL appticefions).
Power can be obtained from any of these connections provided that the total does not exceed
the rated capacity of the terminals.
Consuk the specifications for the devices being connected to detenine the Wwer requirements
for your installation.
4.7.
PROGRAMMER CONNECTION
The section of the PC bard labeled EZ-MATE Programmer is not used on the XL4 system. Do not
attempt to make any connations.
4.8.
JP1
Adding a jumper to JPI causes eaflh ground to become the system ground. Atiemately this can
be performed by connecting terminal 34 to 18.
4.9.
J~
Jumper 2 is used in conjunction with the apphcafion of relay #1. JP2 should be cut if relay #1 is
being used with d~ contacts, or left mnnected it relay #1 is being used as a bell outDut.
4.10.
DEFAULT RESET
Shorting TP1 to TP2 will cause the panel to revert to the original panel default values. This should
only be petiormed if the programming status is unknown and the panel defauks are desired. The
XL-4 Defauh values can be viewed in the LCD Keypad Programming Manual.
To perfom a default reset remove all ~wer to the panel, AC& DC. Short TP1 & TP2 and while
short is still intact reapply power AC then DC. Wati 8 to 10 seconds then remove the short w~le the
unit is still powered. The system default reset may take 20 to 30 seconds.
NOTE: If the INSTALLER LOCKOUT option has been selected wtihin the programming eequence
then a defauk reset through these pins will pedorm a defauk with the exception of the CSID and
Installer Code,
XL-4 HOOKUP & INSTALLATION Page 12