B 5.5 Tab Control room horn

The notification that an event has occurred can also, in addition to the field horn, be made by a
sound board or relay board (control room horn).
Messages
Tone type
Rel.-T.
Gross Automation, 1725 South Johnson Road, New Berlin, WI 53146, www.ssacsales.com, 800-349-5827
For system message groups S1 to S3 and priority levels 1 to 4 it is possi-
ble to indicate whether the control room horn is to sound when messages
are Coming or Going or for both.
For each priority, several sound files (WAV files) may be entered with or
without extensions. These files will be played back in succession and with
no interval.
The system loads the files from the standard DigiVis folder
\Freelance\wave\... It is also possible to specify the full path and filename,
e.g. c:\winnt\media\... The length of this input must not exceed 100 char-
acters. In accordance with the Play sound files in setting, the DigiVis
sound system will play the selected files for coming and going messages.
If the notification takes place by means of signals, which are produced by
devices connected to the relay card, the relay terminal (1 to 8 possible)
for each priority level must be indicated.
Messages and Hints
ts0504us.bmp
B-25