Siemens S7-300 Installation Manual page 52

Automation system
Hide thumbs Also See for S7-300:
Table of Contents

Advertisement

&RQILJXULQJ
5XOH *URXQG WKH FDEOH VKLHOGLQJ
You should always connect both ends of the cable shielding to ground/functional
ground, since this is the only way to achieve good interference suppression in the
higher frequency range.
If you connect only one end of the shielding (that is, at one or the other end of the
cable) to ground, you will merely achieve an attenuation in the lower frequency
range. One-sided shielding connections could be more favorable in situations
• not allowing the installation of an equipotential bonding conductor,
• if analog signals (some mA or µ A) are transmitted,
• or if foil shielding is used (static shielding).
1RWH
Potential differences between two grounding points might cause an
equipotential current flow across shielding connected at both ends. In this case
you should install an additional equipotential bonding conductor..
&DXWLRQ
Always avoid the flow of operating current to ground.
$GGLWLRQDO LQIRUPDWLRQ RQ FDEOH VKLHOGLQJ DQG HTXLSRWHQWLDO ERQGLQJ
are found in the Appendix under the same topic.
5XOH *URXQG WKH ORDG FLUFXLWV
You should always ground the load circuits. This common reference potential
(earth) ensures proper functioning.
7LS: (except for CPU 312 IFM)
If you want to locate a fault to ground, provide your load power supply (Terminal L–
or M) or the isolating transformer with a removable connection to the protective
conductor (see 2YHUYLHZ *URXQGLQJ Number 4).
5-26
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
A5E00203919-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents