Structure Of Station Status 1 (Byte 0) - Siemens S7-300 Installation Manual

Automation system
Hide thumbs Also See for S7-300:
Table of Contents

Advertisement

6WDWLRQ VWDWXV 
Table 11-13 Structure of station status 1 (byte 0)
%LW
 DP slave cannot be addressed by DP master.
0
 DP slave is not ready for data exchange.
1
 Configuration data sent by DP master to the DP
2
slave is inconsistent with slave configuration.
 Diagnostic interrupt, generated by a RUN to
3
STOP transition on the CPU or by the SFB 75
 Diagnostic interrupt, generated by a STOP to
RUN transition on the CPU or by the SFB 75
 Function not supported; e.g. changing the DP
4
address at software level
 This bit is always "0".
5
 DP slave type inconsistent with software
6
configuration.
 DP slave was configured by a DP master other
7
than the master currently accessing the slave.
6WDWLRQ 6WDWXV 
Table 11-14 Structure of station status 2 (byte 1)
%LW
 The DP slave requires new parameters and configuration.
0
 A diagnostic message was received. The DP slave cannot resume operation until the error
1
has been cleared (static diagnostic message).
 This bit is always "1" if a DP slave exists with this DP address.
2
 The watchdog monitor is enabled on this DP slave.
3
 DP slave has received control command "FREEZE".
4
 DP slave has received control command "SYNC".
5
 This bit is always "0".
6
 DP slave is disabled, that is, it has been excluded from cyclic processing.
7
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
A5E00203919-01
'HVFULSWLRQ
7HVWLQJ IXQFWLRQV DQG 'LDJQRVWLFV
Is the correct DP address set on the DP
slave?
Is the bus connector in place?
Does the DP slave have power?
Correct configuration of the RS485
Repeater?
Perform a reset on the DP slave.
Wait for the slave to complete start-up.
Was the software set for the correct
station type or DP slave configuration?
You can read the diagnostic data.
Check configuration data.
-
Was the software set for the right station
type? (parameter assignment error)
The bit is always 1 if, for example, you are
currently accessing the DP slave via PG or
a different DP master.
The configuring master's DP address is
located in the "Master PROFIBUS address"
diagnostics byte.
'HVFULSWLRQ
5HPHG\
11-23