Wiring Diagram - Panasonic Network Adaptor Specification Sheet

Programmable controller
Hide thumbs Also See for Network Adaptor:
Table of Contents

Advertisement

FP-e Series
Technical data
Transistor NPN output specifications
(For Y0 to Y4)
Item
Insulation method
Optical coupler
Output type
Open collector
Rated load voltage
5 to 24 V DC
Operating load voltage range
4.75 to 26.4 V DC
Max. load current
0.5 A
Max. surge current
1 A
Output points per common
5 points/common
OFF state leakage current
100 µA or less
ON state voltage drop
1.5 V or less
50 µs or less (For Y0 and Y1),
OFF to ON
1 ms or less (For Y2,Y3 and Y4)
Response
time
50 µs or less (For Y0 and Y1),
ON to OFF
1 ms or less (For Y2,Y3 and Y4)
Voltage
21.6 to 26.4 V DC
External power
supply (For driving
6 mA/point (For Y0 and Y1)
Current
internal circuit)
3 mA/point (For Y2, Y3, and Y4)
Surge absorber
Zener diode
Operating indicator
LCD display (I/O monitor mode)
COM. port communication specifications
Item
∗2)
COM. port type
RS232C
Isolation status with
Non-isolated
the internal circuit
Transmission distance
15 m
300, 600, 1200, 2400,
Baud rate
∗3)
4800, 9600, 19200 bit/s
Communication method
Half-duplex
Synchro system
Synchronous communication method
Stop bit: 1 bit/2 bit
Parity: Not available/Available
(Odd number/Even number)
Transmission format
Data length 7 bit/8 bit
Beginning code: STX available/STX not available
Ending code: CR/CR+LF/not available/ETX
Data output order
Starting from 0 bits per character
No. of connected units
• General-purpose
Communication mode
communication
• Computer link
Dimensions
48
70
7.5
.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Relay output specifications
(Y5)
Description
Output type
Rated control capacity
Output points per common
Response time
Life time
Surge absorber
Operating indicator
∗1)
∗1) When communicating between FP-e and other devices, it is recommneded to perform
Description
resend processing.
∗2) For RS232C wiring, be sure to use shielded wires for higher noise immunity.
RS485
∗3) Set the baud rate of RS485 with the FP-e system register and FP-e internal switch.
Set the baud rate of RS232C with the FP-e system register.
Isolated
∗4) When sending a command from the FP-e is completed in RS485 communication, send a
response from the receiving device to the FP-e after the following time has elapsed:
1200 m
9600 bit/s: 2 ms or longer
It takes at least 1 scan time (at least 2 ms) for the FP-e to send back a response after
∗4)
9600,19200 bit/s
received the command.
∗5) When our C-NET Adapter or RS485 device other than recommended is connected in the
system, the maximum connection number is limited to 32 units.
∗6) For a RS485 converter on the computer side, SI-35 (from LINE EYE Co., Ltd.) is
recommended.
When SI-35 is used in the system, up to 99 units can be connected.
∗5) ∗6)
99

Wiring diagram

(mm)
Input connector
(Standard type)
44.5
COM
X0
X1
X2
X3
X4
X5
X6
X7
Output connector
+
Y0 to Y4
L
Y0
L
Y1
L
Y2
L
Y3
L
Y4
YC
L
Y5
Power
COM
Item
Description
Normally open (1 Form A)
2 A 250 V AC, 2 A 30 V DC
1 point/common
OFF to ON
Approx. 10 ms
ON to OFF
Approx. 8 ms
7
Mechanical
Min. 2 × 10
operations
Electrical
Min. 10
5
operations (resistive load)
None
LCD display (I/O monitor mode)
19200 bit/s: 1 ms or longer
19200 bit/s
9600 bit/s
(Thermocouple input type)
COM
COM
X0
X1
X2
Xn
X3
X4
X5
A0+
TC0
A0−
Power supply/COM. port connector
A1+
(RS232C type)
TC1
A1−
24 V DC
Send data (Output)
COM. port
(+)
Receive data (Input)
(RS232C)
Signal Ground
(RS485 type)
(−)
(Terminal station)
+
24 V DC
Y5
Ground
COM. port
(RS485)
Short
E
COM
+
Ground
SD
RD
SG
(Ordinary station)
+
24 V DC
Ground
COM. port
(RS485)
E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp-e seriesAfpe224300Afpe224302Afpe224305Afpe214325Afpe214322

Table of Contents