Modes of Operation

Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (59)

The test report sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the
message is to be sent every 24 hours, leave the factory default entry of '0'. If other test report times
are needed, enter 1 = 12 hour, 2 = 8 hour or 3 = 6 hour.
AC Loss Reporting Delay (60)
Enter a digit of 0 - 9 or A - F corresponding to the number of hours to be delayed in reporting the
loss of AC power. The factory default is '2' for 2 hour delay. The valid entries are '0' = no delay;
'1' = 1 hours; '2' = 2 hours; '3' = 6 hours; '4' = 7 hours; '5' = 8 hours; '6' = 9 hours; '7' = 10 hours;
'8' = 11 hours; '9' = 12 hours; 'A' = 13 hours; 'B' = 14 hours; 'C' = 15 hours; 'D' = 16 hours; 'E' = 17
hours; 'F' = 18 hours.
NOTE: Use when the host panel has a dedicated relay output. Verify the delay period
programmed at the host panel. Location 60 is valid for all inputs programmed as AC Loss.
Backup Reporting (61)
Leaving address 61 at '0' means that reports will be transmitted to the secondary Central Station
phone number only if attempts to communicate to the primary Central Station phone number are
unsuccessful. Programming a '1' causes all reports to be transmitted to both the primary and sec-
ondary Central Station phone numbers. Programming a '2' causes reports to go to the first available
receiver.
CAUTION:
!
DO NOT ALTER THIS ENTRY WHILE THE DIGITAL COMMUNICATOR IS ACTIVE.
Reserved for Future Use (62)
Reserved for Future Use (63)
Communicator Enable/Disable (64)
Leaving address 64 at the factory default setting of '0' prevents the digital communicator from
transmitting status information to the Central Station(s). An entry of '1' in this location enables
communication to the Central Station(s).
Note that upon power-up, the 411/411UD will immediately annunciate a DACT trouble since the
communicator is factory defaulted to 'communicator disabled' at program location 64.
Input Channel Function Selections - When selecting Input Channel functions, be certain to match
the host panel relay output functions with the Input Channel functions. Test all wiring connections
completely. All Input Channels require Normally Open contact closure to trigger. Input Channels
do not latch.
Input Channel 1 Function Selection (65)
Factory default for Channel 1 is '0' for activation on Fire Alarm. Enter '1' for Host Control Panel
Trouble; '2' for Fire Supervisory; '4' for AC Loss.
Input Channel 2 Function Selection (66)
Factory default for Channel 2 is '1' for activation on Host Control Panel Trouble. Enter '0' for Fire
Alarm; '2' for Fire Supervisory; '4' for AC Loss.
1. Changing the input function will automatically change the corresponding Primary and
Secondary event codes to reflect the new input function. The Communication Format
should be programmed first, followed by the Input Channel Function.
36
57: enter 0 - 5
58: enter 0 - 9