Installation
The factory default programming for each channel is as follows:
•
Channel 1 - fire alarm
•
Channel 2 - host control panel trouble
•
Channel 3 - fire supervisory
•
Channel 4 (411UD Only) - AC Loss
Channel Labels
Note that space is provided for labeling the function of each channel. Write the function that has
been programmed for each channel in the white boxes located to the right of the channel designator.
Normally Open Contact Device
2.4 Output Circuits
Relays
The 411/411UD provides one Form-C relay rated for 2.0 amps @ 30 VDC (resistive). The relay is
programmable for activation on fire alarm, host panel trouble, fire supervisory, total communica-
tion failure, AC loss and DACT trouble.
One Form-C Relay
(nonsupervised)
Relay Label
Note that space is provided for labeling the function of the relay. Write the function that has been
programmed for the relay in the white box located below the relay designator.
18
Inputs are
power-limited
2.2K ELR
P/N 27070
Figure 2.2 Style B Channel Connections
Relay Label
Figure 2.3 Programmable Relay
Channel/Input Labels
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
Output Circuits