Product Description
– Primary Central Station number communication fault
– Secondary Central Station number communication fault
– system off-normal (local Program Mode entered)
– 24 Hour normal test
– 24 Hour abnormal test (24 hour test message with previously reported alarm or trouble still
active)
•
Individual LEDs for:
– Communication Fail (visible with cover on)
– DACT Trouble (visible with cover on) - 411UD only
– Channel Active (visible with cover on) - 411UD only
– Primary Phone Line (PH1) active - 411UD only
– Secondary Phone Line (PH2) active - 411UD only
•
Piezo sounder
•
Local piezo silence switch which silences onboard piezo sounder (accessible without removing
cover)
•
Real time clock
•
Extensive transient protection
•
One Form-C relay, fully programmable to activate for the following conditions:
– fire alarm
– host control panel trouble
– fire supervisory
– total communication failure
– AC loss
– DACT trouble (factory default for relay)
•
PK-411 Remote Upload/Download Kit - 411UD only
•
'Dialer runaway' feature
•
Trouble Resound - if a trouble is silenced and the cause of the trouble is not cleared, the panel
will resound the trouble buzzer every midnight, until the trouble is cleared
1.2 Specifications
Operating Power
The 411/411UD may be powered from UL listed control panels that output nonresettable and
power-limited 12 or 24 VDC power. The configuration of Jumper J4 determines whether 12 VDC
power is to be supplied directly to the 411/411UD circuit board or 24 VDC power is to be supplied
and then internally regulated down internally to 12 VDC.
DC Power - TB1 Terminals 4(+) and 5(-), Terminal 6 is Earth Ground
•
J4 Jumper shorted on pins 2 and 3 - Filtered, nonresettable and power-limited 24 VDC
(nominal) power must be supplied at TB1 Terminals 4(+) and 5(-). UL-listed operating range
is 17 to 28 VDC. Current requirements are 64 mA in standby and 120 mA
communicating.
•
J4 Jumper shorted on pins 1 and 2 - Filtered, nonresettable and power-limited 12 VDC
(nominal) power must be supplied at TB1 Terminals 4(+) and 5(-). UL-listed operating range
is 9.8 to 14 VDC. Current requirements are 88 mA in standby and 140 mA
communicating.
1. A maximum of 200 mA is possible with all input channels shorted, the 411/411UD communicating,
the Programmer connected, and Lamp Test active.
10
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
Specifications