Goodman GMVM Service Instructions Manual page 24

96% modulating gas furnaces & accessories
Table of Contents

Advertisement

PRODUCT DESIGN
S
V
R
PECIAL
ENTING
EQUIREMENTS
C
ANADA
All installations in Canada must conform to the requirements
of CSAB149 code. All vent system components, including
primer and cement, must be listed to ULC S636. The certi-
fied pipe and fittings should be clearly marked with the ULC
standard "S636". The primer and cement used must be of the
same manufacturer as the vent system. For Royal Pipe Sys-
tem 636; use GVS-65 Primer (Purple) and GVS-65 PVC
Solvent Cement. For IPEX System 636, use PVC/CPVC
Primer, Purple or clear. Use PVC Solvent Cement (Gray).
For Canadian installations, ABS may be used as a combus-
tion air pipe only. ABS is not an approved vent material in
Canada. If ABS is used as a combustion air pipe, it must be
CSA certified. Always follow the manufacturer's instructions
in the use of primer and cement. Do not use primer and ce-
ment around potential sources of ignition. Do not use primer
or cement beyond its expiration date.
The vent can be run through an existing unused chimney
provided the space between the vent pipe and the chimney is
insulated and closed with a
flashing.
S
F
C
TANDARD
URNACE
ONNECTIONS
It is the responsibility of the installer to ensure that the piping
connections to the furnace are secure, airtight, and adequately
supported.
As shipped, attachment "couplings" for vent/flue and combustion
air intake pipe connections are provided on the furnace's top cover
(upflow) or basepan (counterflow). To use the standard connec-
tions, field supplied vent/flue pipe and combustion air intake pipe
(when applicable) should be secured directly to the furnace at
these locations.
V
/F
P
ENT
LUE
IPE
Vent/flue pipe can be secured to the vent/flue coupling using the
rubber coupling and worm gear hose clamps provided with this
furnace (see "Standard Connections" figure). The rubber coupling
allows separation of the vent/flue pipe from the furnace during
servicing. Combustion Air and Vent piping should be routed in a
manner to avoid contact with refrigerant lines, metering devices,
condensate drain lines, etc.
24
F
I
OR
NSTALLATIONS
weather-tight, corrosion-resistant
I
C
A
N
OMBUSTION
IR
D
V
I
IRECT
ENT
NSTALLATIONS
On upflow units secure the combustion air intake pipe directly to
the air intake coupling. On counterflow units secure the com-
bustion air intake pipe to the air intake coupling using the rubber
coupling and worm gear hose clamps provided with the unit. The
counterflow rubber coupling allows service removal of air intake
piping internal to the furnace blower compartment.
N
-D
V
ON
IRECT
ENT
A minimum of one 90° elbow should be installed on the combus-
tion air intake "coupling" to guard against inadvertent blockage.
COMBUSTION
AIR PIPE
(DIRECT VENT ONLY)
90 PVC
ELBOW
(NON-DIRECT VENT)
OR
UPFLOW
E
DGES OF SHEET METAL HOLES MAY BE SHARP
PRECAUTION WHEN REMOVING HOLE PLUGS
A
V
LTERNATE
ENT
The alternate vent/flue location is the large hole directly in line
with the induced draft blower outlet. To use the alternate vent/flue
location refer to the following steps and the "Alternate Vent/Flue
Location" figure.
NOTE: Counterflow instructions follow the upflow instructions.
1. Remove and save the four screws securing the vent/
flue coupling to the furnace top panel.
Counterflow units.
Remove and save the four screws securing the vent/
flue coupling to the furnace basepan. Also remove the
three screws securing the furnace's internal vent/flue
piping to the blower deck.
P
IPE
I
NSTALLATIONS
COMBUSTION
VENT/FLUE
(DIRECT VENT ONLY)
PIPE
RUBBER
90 PVC
COUPLING
ELBOW
WITH WORM
(NON-DIRECT VENT)
GEAR CLAMPS
OR
Standard Connections
WARNING
. U
SE GLOVES AS A
.
/F
L
LUE
OCATION
VENT/FLUE
AIR PIPE
PIPE
RUBBER
COUPLINGS
WITH WORM
GEAR CLAMPS
COUNTERFLOW

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

AcvmGcvmAmvm

Table of Contents