Specification
Input requirements
Rated input voltage
Rated input frequency
Maximum input current per
line cord
Maximum input power per
line cord

Three-phase power (International)

Specification
Power cords (2)
Output
Input requirements
Rated input voltage
Rated input frequency
Maximum input current per
line cord
Maximum input power per
line cord
*Rated 220 VAC to 240 VAC line-to-neutral. The enclosure does not operate from higher line-to-line voltage with the
WYE wall plug configuration. Input AC modules are configured to provide 220 VAC to 240 VAC to the power supplies
in this system.
2450W Platinum Hot Plug
Redundant Power Supply
200 VAC to 208 VAC line to line
3-phase delta
50 Hz to 60 Hz
22.9 A at 200 VAC
22 A at 208 VAC
7920 VA
2450W Platinum Hot Plug
Redundant Power Supply
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
2450 W
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
50 Hz to 60 Hz
12.2 A at 220/380 VAC
11.2 A at 240/415 VAC
8064 VA
2650W Platinum Hot Plug
Redundant Power Supply
200 VAC to 208 VAC line to line
3-phase delta
50 Hz to 60 Hz
25 A at 200 VAC
24 A at 208 VAC
8640 VA
2650W Platinum Hot Plug
Redundant Power Supply
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
2650 W
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
50 Hz to 60 Hz
13.1 A at 220/380 VAC
12 A at 240/415 VAC
8646 VA
Specifications 58