Configuring parameters to be read from the drive

The ACS3XX_COM_MOD_RTU function block can read up to 8 parameters from the
ACS3xx drive.
The ACS3xx drive parameters 53.10...53.17 determine which parameters are read from
the drive. Give the values in the format XXYY, where XX is the parameter group and YY is
the parameter index of the parameter to be read. For example, the value 104 corresponds
to parameter 01.04 CURRENT.
Set parameter 53.10 to either 101 (calculated motor speed) or 103 (calculated drive output
frequency). You can freely choose which parameters to map to parameters 53.11...53.17.
For instructions on how to set parameter values, see ACS355 user's manual
(3AUA0000066143 [English]).
If more than three parameters are configured to be read, change the value of
NVAR_READ in the ACS3XX_COM_MOD_RTU function block as instructed below.
1. In CoDeSys, go offline by clicking Online > Logout.
2. In the ACS3XX_COM_MOD_RTU function
block, change the value of NVAR_READ to
correspond to the number of parameters
read + 1 (the number includes the status
word).
3. Go back online by clicking Online > Login.
An Online Change dialog opens.
4. Click Yes.
The visualization is updated to reflect the changes made.
5. To keep the changes for the next reboot, click Online > Create boot project.

Configuration example

In this example, six parameters are configured to be read from an ACS355 drive by the
function block. The following values are given to parameters 53.10...53.16:
Parameter set
Value
in the drive
53.10
101
53.11
104
53.12
305
53.13
110
53.14
114
53.15
105
Parameter read from
the drive
01.01 SPEED & DIR
01.04 CURRENT
03.05 FAULT WORD 1
01.10 DRIVE TEMP
01.14 RUN TIME (R)
01.05 TORQUE
Function
Calculated motor speed in rpm. A negative value
indicates reverse direction.
Measured motor current (1 = 0.1 A).
A 16-bit data word that indicates faults in the drive.
Measured IGBT temperature in (1 = 0.1 °C).
Elapsed drive running time in hours.
Ratio of calculated motor torque to the motor nomi-
nal torque (1 = 0.1% of the nominal torque).
Customization 21