4. Operating condition

Appliance should be working indoor, with ambient temperature from -25 °C to +50 °C and humidity up to 90 %, not
condensing water.

5. Technical parameters

Functional
Diagnostic
Auxiliary
contacts
Operating ambient temperature
Storage & transportation temperature
Humidity
Protection class
8
No one should touch terminals with metallic objects, when
appliance is under voltage.
It is forbidden to place any objects close to or into ventilation
gaps of the device.
In case of improper work or failure, it is necessary to
separate appliance from system and replace with a new
device.
Rated operational voltage
Max. operational current
Voltage range
Nominal frequency
Time delay
Threshold voltage
Selfconsumption
Rated control supply voltage
Voltage range
Nominal frequency
Selfconsuption
Rated control circuit voltage
Ue
100 / 110
Iemax
10 A/0,2s
U
0-110
fn
50/60
td
0.4, 1.4, 2.4, 3.4
Ut
20, 25 ,30
P
<0.1
US
100/V3, 100/3
U
33-110
fn
50/60
P
< 2
D
230 (max. 100mA)
UC
220 (max. 100mA)
-
-25°C ... +50
-
-40°C ... +85
-
up to 90
-
1VLM000651, Rev.3, en 2014.01.21
V AC
V AC
Hz
s
V
W
V AC
V AC
Hz
W
V AC
V DC
°C
°C
%
IP 20