Connecting The Power Terminal - Samsung AC052HBMPKH Manual

Hide thumbs Also See for AC052HBMPKH:
Table of Contents

Advertisement

Connecting the cable
AA

Connecting the Power Terminal

 Connect the cables to the terminal board using the compressed ring terminal.
 Cover a solderless ring terminal and a connector part of the power cable and then connect it.
Nominal
Nominal
dimensions
dimensions
Standard
for cable
for screw
dimension
2
2
[mm
(inch
)]
[mm(inch)]
[mm(inch)]
4(3/8)
9.5(3/8)
4/6
(0.006/
0.009)
8(3/16)
15(9/16)
10(0.01)
8(3/16)
15(9/16)
16(0.02)
8(3/16)
16(10/16)
8(3/16)
12(1/2)
25(0.03)
8(3/16)
16. 5 (10/16)
8(3/16)
16(10/16)
35(0.05)
8(3/16)
22(7/8)
50(0.07)
8(3/16)
22(7/8)
70(0.10)
8(3/16)
24(1)
 Connect the rated cables only.
 Connect using a driver which is able to apply the rated torque to the screws.
 If the terminal is loose, fire may occur caused by arc. If the terminal is connected too firmly, the terminal may be damaged.
M4
12.0~15.0
• When connecting cables, you can connect the cables to the electrical part or connect them through the holes
below depending on the spot.
• Run transmission wiring between the indoor and outdoor units through a conduit to protect against external
forces, and feed the conduit through the wall together with refirgerant piping.
• Remove all burrs at the edge of the knock-out hole and secure the cable to the outdoor knock-out using lining and
bushing with an electrical insulation such as rubber and so on.
• Must keep the cable in a protection tube.
• Keep distances of 50mm or more between power cable and communication cable.
• When the cables are connected through the hole, remove the Plate bottom.
14
B
D
Standard
Allowance
Allowance
dimension
[mm(inch)]
[mm(inch)]
[mm(inch)]
±0.2
+0.3(+0.011)
5.6(1/4)
(±0.007)
-0.2(-0.007)
±0.2
+0.3(+0.011)
7.1(1/4)
(±0.007)
-0.2(-0.007)
±0.2
+0.3(+0.011)
9(3/8)
(±0.007)
-0.2(-0.007)
±0.3
+0.5(+0.019)
11.5(7/16)
(±0.011)
-0.2(-0.007)
±0.3
+0.5(+0.019)
13.3(1/2)
(±0.011)
-0.2(-0.007)
±0.3
+0.5(+0.019)
13.5(1/2)
(±0.011)
-0.2(-0.007)
±0.4
+0.5(+0.019)
17.5(11/16)
(±0.015)
-0.4(-0.015)
Tightening Torque (kgf • cm)
Silver solder
d1
E
Standard
Min.
Allowance
dimension
[mm
[mm(inch)]
[mm(inch)]
(inch)]
(inch)]
±0.2
6
3.4(1/8)
(±0.007)
(1/4)
±0.2
7.9
4.5(3/16)
(±0.007)
(5/16)
±0.2
9.5
5.8(1/4)
(±0.007)
(5/16)
±0.2
11
7.7(5/16)
(±0.007)
(3/8)
±0.2
12.5
9.4(3/8)
(±0.007)
(1/2)
±0.3
17.5
11.4(7/16)
(±0.011)
(11/16)
±0.4
18.5
13.3(1/2)
(±0.015)
(3/4)
AC power : L,N,1(L),2(N), Communication : F1, F2
F
L
d2
Min.
Max.
Standard
Allowance
[mm
[mm
dimension
[mm(inch)]
(inch)]
[mm(inch)]
5
20
4.3
+ 0.2(+0.007)
(3/16)
(3/4)
(3/16)
0(0)
9
28.5
8.4
+ 0.4(+0.015)
(3/8)
(1-1/8)
(1-3/16)
0(0)
9
30
8.4
+ 0.4(+0.015)
(3/8)
(1-3/16)
(1-3/16)
0(0)
13
33
8.4
+ 0.4(+0.015)
(1/2)
(1-5/16)
(1-3/16)
0(0)
15
8.4
(5/8)
(1-3/16)
34
+ 0.4(+0.015)
(1-3/8)
0(0)
13
8.4
(1/2)
(1-3/16)
13
38
8.4
(1/2)
(1-1/2)
(1-3/16)
+ 0.4(+0.015)
0(0)
13
43
8.4
(1/2)
(1- 11/16)
(1-3/16)
14
50
8.4
+ 0.4(+0.015)
(9/16)
(2)
(1-3/16)
0(0)
20
51
8.4
+ 0.4(+0.015)
(3/4)
(2)
(1-3/16)
0(0)
t
Min.
[mm
(inch)]
0.9
(0.03)
1.15
(0.04)
1.45
(0.05)
1.7
(0.06)
1.8
(0.07)
1.8
(0.07)
2.0
(0.078)