460V, 60Hz, 3-Phase Heat Pump Units - LG Multi IV Engineering Manual

Table of Contents

Advertisement

ELECTRICAL DATA
ARUN Series Heat Pump Outdoor Units
Table 24: 460V, 60Hz, 3-Phase Heat Pump Units.
Nom.
Unit Model Nos.
Comp.
Tons
Qty.
6.0
ARUN072DTE4
1
8.0
ARUN096DTE4
1
10.0 ARUN121DTE4
1
12.0 ARUN144DTE4
2
14.0 ARUN168DTE4
2
16.0 ARUN192DTE4
2
18.0 ARUN216DTE4
3
20.0 ARUN240DTE4
3
22.0 ARUN264DTE4
3
24.0 ARUN288DTE4
4
26.0 ARUN313DTE4
4
28.0 ARUN337DTE4
4
26.0 ARUN312DTE4
4
28.0 ARUN336DTE4
4
30.0 ARUN360DTE4
4
32.0 ARUN384DTE4
5
34.0 ARUN408DTE4
5
36.0 ARUN432DTE4
6
38.0 ARUN456DTE4
6
40.0 ARUN480DTE4
6
42.0 ARUN504DTE4
6
For component model nos. see the specification tables on p. 15-19.
Voltage tolerance is 414-528V.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
32 | PRODUCT DATA
Compressor (Comp.)
Motor Amps
Motor RLA (Ea.)
Frame
1
2
Comp.
Comp.
Comp.
Comp.
Comp.
A
B
A
B
11.7
-
-
-
16.5
-
-
-
17.1
-
-
-
12.9
12.9
-
-
13.9
13.9
-
-
11.7
-
17.1
-
11.7
-
12.9
12.9
16.5
-
12.9
12.9
17.1
-
12.9
12.9
12.9
12.9
12.9
12.9
13.9
13.9
12.9
12.9
13.9
13.9
13.9
13.9
11.7
-
16.5
-
12.9
16.5
-
16.5
-
12.9
16.5
-
17.1
-
12.9
16.5
-
16.2
12.9
16.2
17.1
-
16.2
12.9
16.2
16.2
12.9
16.2
12.9
16.2
16.2
12.9
16.2
12.9
16.2
16.2
12.9
16.2
12.9
16.2
16.2
12.9
16.2
12.9
16.2
©
Condenser Fan
Motor(s)
Amps
FLA (Ea.)
Fan
Frame
Qty.
3
1
2
Comp.
A
B
-
-
1
2.1
-
-
-
2
2.6
-
-
-
2
2.6
-
-
-
2
2.6
-
-
-
2
2.6
-
-
-
3
2.1 2.6
-
-
3
2.1 2.6
-
-
4
2.6 2.6
-
-
4
2.6 2.6
-
-
4
2.6 2.6
-
-
4
2.6 2.6
-
-
4
2.6 2.6
12.9
5
2.1 2.6 2.6 16.7 23.2 31.6 25
12.9
6
2.6 2.6 2.6 23.2 23.2 31.6 35
12.9
6
2.6 2.6 2.6 23.2 24.0 31.6 35
12.9
6
2.6 2.6 2.6 23.2 35.8 35.8 35
12.9
6
2.6 2.6 2.6 24.0 35.8 35.8 40
12.9
6
2.6 2.6 2.6 35.8 35.8 35.8 50
12.9
6
2.6 2.6 2.6 35.8 35.8 35.8 50
12.9
6
2.6 2.6 2.6 35.8 35.8 35.8 50
12.9
6
2.6 2.6 2.6 35.8 35.8 35.8 50
Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RFA = Recommended Fuse Amps.
MCA
MOCP
Frame
Frame
1
2
3
1
2
3
-
16.7
-
-
25
-
-
23.2
-
-
35
-
-
24.0
-
-
40
-
-
31.6
-
-
40
-
-
33.9
-
-
45
-
-
16.7 24.0
-
25
40
-
16.7 31.6
-
25
40
-
23.2 31.6
-
35
40
-
24.0 31.6
-
40
40
-
31.6 31.6
-
40
40
-
31.6 33.9
-
40
45
-
33.9 33.9
-
45
45
35
35
40
50
50
50
50
50
50
RFA
Frame
3
1
2
3
-
25
-
-
-
30
-
-
-
30
-
-
-
40
-
-
-
45
-
-
-
25
30
-
-
25
40
-
-
30
40
-
-
30
40
-
-
40
40
-
-
50
50
-
-
50
50
-
40
25
30
40
40
30
30
40
40
30
30
40
50
30
50
50
50
30
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

Hide quick links: