REFRIGERANT PIPING DESIGN
Piping Design Guideline Summary
The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations.
Combination Y-branch Pipe and Header Pipe Sizing When Installing a Dual-
Frame System
Example: Five (5) indoor units connected
ODU: Outdoor Units.
IDU: Indoor Units.
A: Main Pipe from Outdoor Unit to First Y-branch.
B: Y-branch to Y-branch / Header.
C: Y-branch / Header to Indoor Unit.
• Larger-capacity outdoor units must be the master in a multi-
frame system.
• Single-compressor outdoor units (72,000 Btu/h capacity)
cannot be the master outdoor units in a multi-frame system.
• Master outdoor unit capacity must be greater than or equal
to the slave outdoor unit capacity.
• Y-branches and other header branches cannot be installed
downstream of the initial header branch.
See pages 122-123 for refrigerant pipe diameter and pipe
length tables.
Table 34: Main Pipe (A) Diameter from Outdoor Unit to First Y-branch / Header Branch.
Pipe diameter when pipe
length is <295 feet
ODU
(Standard)
Capacity
(ton)
Liquid pipe
Vapor pipe
(inches OD)
(inches OD)
6
3/8Ø
3/4Ø
8
3/8Ø
7/8Ø
10-12
1/2Ø
1-1/8Ø
12-14*
5/8Ø
1-1/8Ø
14-18
5/8Ø
1-1/8Ø
20
5/8Ø
1-3/8Ø
22-28
3/4Ø
1-3/8Ø
30-42
3/4Ø
1-5/8Ø
*ARUN145BTE4 / ARUN145DTE4 and ARUN169BTE4 / ARUN169DTE4 only.
Table 36: Indoor Unit Connecting Pipe from Branch (C).
Indoor Unit Capacity
1
9,600-24,200 Btu/h 4-way 3 feet x 3 feet Cassette and 15,400-24,200 Btu/h High Static Ducted indoor units have 3/8Ø (liquid) and 5/8Ø
1
(vapor).
122 |
Pipe diameter when pipe Pipe diameter when height
Liquid pipe
Vapor pipe
(inches OD)
(inches OD)
1/2Ø
7/8Ø
1/2Ø
1-1/8Ø
5/8Ø
No Increase
3/4Ø
1-1/4Ø
3/4Ø
1-1/4Ø
3/4Ø
No Increase
7/8Ø
1-1/2Ø
7/8Ø
No Increase
Liquid pipe (inches OD)
1/4Ø
3/8Ø
3/8Ø
©
Slave ODU
Master ODU
A
Y-branch
(first)
B
Y-branch
(second)
is >164 feet
Liquid pipe
Vapor pipe
(inches OD
(inches OD)
1/2Ø
No Increase
1/2Ø
No Increase
5/8Ø
No Increase
3/4Ø
No Increase
3/4Ø
No Increase
3/4Ø
No Increase
7/8Ø
No Increase
7/8Ø
No Increase
Vapor pipe (inches OD)
1/2Ø
5/8Ø
3/4Ø
Y-branch
To
outdoor unit
Header
B
C
C
IDU
IDU
C
C
IDU
Table 35: Refrigerant Pipe Diameter (B) from
Y-branch to Y-branch / Header.
Downstream Total
Liquid pipe
Capacity of IDUs
(inches OD)
(Btu/h)
1
1/4Ø
3/8Ø
3/8Ø
3/8Ø
1/2Ø
5/8Ø
5/8Ø
3/4Ø
3/4Ø
1
For the first branch pipe, use the branch pipe that matches main
pipe A diameter.
To indoor units
Brazed Cap
C
IDU
IDU
Vapor pipe
(inches OD)
1/2Ø
5/8Ø
3/4Ø
7/8Ø
1-1/8Ø
1-1/8Ø
1-3/8Ø
1-3/8Ø
1-5/8Ø