LG Multi IV Engineering Manual page 17

Table of Contents

Advertisement

Table 8: Dual-Frame 460V Heat Pump Units, continued.
Combination Unit Model Number
Individual Component Model Numbers
Cooling Performance
Nominal Cooling Cap. (Btu/h)
1
Rated Cooling Cap. (Btu/h)
2
Heating Performance
Nominal Heating Cap. (Btu/h)
1
Rated Heating Cap. (Btu/h)
2
Operating Range
Cooling (°F DB)
3
Heating (°F WB)
Compressor
Inverter Quantity
Oil/Type
Fan (Top Discharge)
Type
Motor Output (kW) x Qty.
Motor/Drive
Cooling
Operation Range (RPM)
Heating
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. to Max. No. Indoor Units/System
Sound Pressure dB(A)
5
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cables
6,7
Heat Exchanger
Material and Fin Coating
Rows/Fins per inch
Piping
8
Liquid Line Conn. (in., OD)
Vapor Line Conn. (in., OD)
Factory Charge lbs. of R410A
1
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
2
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9°F to +122°F.
3
The System Combination Ratio must be between 50–130%.
4
24.0 Ton
ARUN288DTE4
ARUN144DTE4 +
ARUN144DTE4
288,000
274,000
324,000
308,000
14 to 122
-13 to +61
HSS DC Scroll x 4
PVE/FVC68D
Propeller (BLDC)
0.60 x 2 + 0.60 x 2
0 - 1,100
80 - 1,100
20,400
R410A
EEV/Indoor Unit
4
1 - 45
628 + 628
661 + 661
2 x 18
1/2 + 1/2 Braze
1-1/8 + 1-1/8 Braze
23.6 + 23.6
©
26.0 Ton
ARUN313DTE4
ARUN144DTE4 +
ARUN168DTE4
312,000
296,000
351,000
334,000
14 to 122
-13 to +61
HSS DC Scroll x 4
PVE/FVC68D
Propeller (BLDC)
0.60 x 2 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
80 - 1,100
20,400
R410A
EEV/Indoor Unit
1 - 52
62.5
62.5
628 + 628
661 + 661
2 x 18
Copper Tube/Aluminum Fin and GoldFin™/Hydrophilic
3/14
3/14
1/2 + 5/8 Braze
1-1/8 + 1-1/8 Braze
23.6 + 23.6
5
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
6
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
Power wiring cable is field provided and must comply with the applicable local and national codes. See
7
page 32 for detailed electrical data.
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
8
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configura-
tion using LG's computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
GENERAL DATA
28.0 Ton
ARUN337DTE4
ARUN168DTE4 +
ARUN168DTE4
336,000
320,000
378,000
361,000
14 to 122
-13 to +61
HSS DC Scroll x 4
PVE/FVC68D
Propeller (BLDC)
0.60 x 2 + 0.60 x 2
0 - 1,100
80 - 1,100
20,400
R410A
EEV/Indoor Unit
1 - 55
62.5
628 + 628
661 + 661
2 x 18
3/14
5/8 + 5/8 Braze
1-1/8 + 1-1/8 Braze
23.6 + 23.6
PRODUCT DATA | 17