Siemens SIMATIC 6ES7134-4FB01-0AB0 Manual page 20

Et 200s distributed i/o 2ai u st analog electronic module
Table of Contents

Advertisement

Connecting
5.1 Connecting measuring sensors
Abbreviations used
The meanings of the abbreviations in the figures below are as follows:
M+:
M-
M
ANA
M
L+
U
CM
U
ISO
Isolated measuring encoders
The isolated measuring encoders are not connected to the local ground potential. These can
be potential-free. Depending on local conditions or interference, potential differences U
(static or dynamic) can occur between the measuring lines M- of the input channels and the
reference point of the measuring circuit M
To ensure that the permitted value for U
interference, the following applies:
● For the 2 AI U analog input module: Connect M- to M
The following schematic representation illustrates the connection of isolated measuring
encoders to the optically isolated analog input modules.
5
20
Measuring line (positive)
Measuring line (negative)
Analog measuring circuit reference potential
Ground connection
Rated load voltage 24 V DC
Potential difference between inputs and reference potential of the measuring
circuit M
ANA
Potential difference between M
4
Logic
Backplane bus
Ground bus
Central grounding point
Isolated measuring encoders
and central grounding point
ANA
.
ANA
is not exceeded in environments with strong EMC
CM
ANA
1
3
2AI U ST analog electronic module (6ES7134-4FB01-0AB0)
!
2
Manual, 04/2007, A5E01076000-01
CM