Unison Echo™ Wall Mount Station Power Supply w/ Aux Power
Overview
The Echo Wall Mount Station Power Supply with Auxiliary
Power (E-SPM-WM-A) is designed for use with the Echo control
system to supply bus power for up to 16 Echo architectural
control stations on the topology-free EchoConnect control
network and provides 24 Vdc auxiliary power (maximum 36
watts) for Echo devices.
The E-SPM-WM-A also supports connection of up to 16
compatible power panels or distributed controllers over
EchoConnect.
Note:
If you are using Cat5 (or Cat5e) wiring, an
external Echo Cat5 Termination Box (is required.
Contact ETC for ordering details. Control wiring
instructions between the termination box and
this Wall Mount Station Power Supply with
Auxiliary Power are provided with the Cat5
termination box installation instructions.
For use with ETC Dimming and Relay Products.
Installation
Mount the Enclosure to the Wall
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Corporate Headquarters
London, UK
Tel +44 (0)20 8896 1000
Rome, IT
Tel +39 (06) 32 111 683
Holzkirchen, DE
Hong Kong
Tel +852 2799 1220
Web:
www.etcconnect.com
7186M2104
Rev A
Station Power Supply with Auxiliary Power
Remove the front cover of the enclosure
to reveal the four mounting keyholes.
Align the enclosure to the wall and mark
the mounting keyholes. Alternatively,
use the measured keyhole dimensions
located in the graphic (right) to mark the
hole locations for the mounting
hardware.
Drill the holes and install the mounting
hardware.
• Mounting hardware is not
supplied.
• Expose at least 1" (25mm) of
threads for mounting.
Attach the enclosure to the mounting
hardware, where the back side is flush
to the wall, then tighten the mounting
hardware.
Insert a screw into the provided wall anchor point, located between the left side mounting
keyholes of the enclosure. Populating this hole with a screw provides additional security that
the enclosure will not fall from the wall during a seismic condition.
Middleton, WI, USA
Tel +608 831 4116
Service: (UK)
Service: (UK)
service@etceurope.com
Tel +49 (80 24) 47 00-0
Service: (DE)
Service: (Asia)
service@etcasia.com
© 2015 ETC. All Rights Reserved.
Released 2015-06
ETC intends this document to be provided in its entirety.
as viewed from the back panel
11.5"
292mm
Service: (Americas)
service@etceurope.com
techserv-hoki@etcconnect.com
Product information and specifications subject to change.
Page 1 of 4
8.7"
221mm
insert seismic
condition screw
here
10.5"
267mm
service@etcconnect.com
Electronic Theatre Controls, Inc.
14"
356mm
3.15" deep
80mm

Advertisement

loading

Summary of Contents for ETC Unison Echo

  • Page 1 ETC Installation Guide Unison Echo™ Wall Mount Station Power Supply w/ Aux Power Overview The Echo Wall Mount Station Power Supply with Auxiliary Power (E-SPM-WM-A) is designed for use with the Echo control system to supply bus power for up to 16 Echo architectural...
  • Page 2 ETC Installation Guide Wall Mount Station Power Supply with Auxiliary Power Rough-In Conduit and Wiring Knockouts are provided on top and bottom for conduit access into the enclosure. All wiring terminations are accessible from the front of the enclosure with the cover removed.
  • Page 3 16 compatible power panels or distributed power controllers. EchoConnect is a bidirectional protocol that uses one pair of wires (data+ and data-) for both data and power. ETC recommends using Belden 8471 (or approved equal) Class II wire.
  • Page 4: Status Indicators

    ETC Installation Guide Wall Mount Station Power Supply with Auxiliary Power Status Indicators When power is applied, the “Bus Power” and “Aux Power” LEDs located on the front panel illuminates. Bus Power LED If a fault is discovered in the control wiring, the Bus Power LED turns off and the Fault indicator will illuminate.