Installing The Refrigerant Piping - Mitsubishi Electric city multi pfky-p-vhm-e Installation Manual

Indoor unit for building application
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
4. Installing the refrigerant piping
B
45±2°
Fig. 4-1
A Flare cutting dimensions
Copper pipe O.D.
Flare dimensions
(mm)
øA dimensions (mm)
ø6.35
ø9.52
12.8 - 13.2
ø12.7
16.2 - 16.6
ø15.88
19.3 - 19.7
ø19.05
22.9 - 23.3
B Refrigerant pipe sizes & Flare nut tightening torque
C Do not apply refrigerating machine oil to the screw portions.
(This will make the flare nuts more apt to loosen.)
D Be certain to use the flare nuts that are attached to the main unit.
(Use of commercially-available products may result in cracking.)
Liquid pipe
Tightening
Pipe size O.D.
torque.
(mm)
(N·m)
P32/40
ODø6.35 (1/4")
14 - 18
P50
ODø9.52 (3/8")
14 - 18*
* Connect the joint with the following pipes: Liquid and gas pipes of P50.
E Apply refrigerating machine oil over the entire flare seat surface.
 PKFY-P·VHM-E
6
C
8.7 - 9.1
R407C or R22
Gas pipe
Tightening
Pipe size O.D.
torque.
(mm)
(N·m)
ODø12.7 (1/2")
49 - 61
ODø15.88 (5/8")
49 - 61*
4.1. Connecting pipes (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C or
more, thickness of 12 mm or more).
• The indoor parts of the drain pipe should be wrapped with polyethylene foam
D
insulation materials (specific gravity of 0.03, thickness of 9 mm or more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before
tightening flare nut.
• Use two wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections.
Insulate carefully.
Warning:
When installing the unit, securely connect the refrigerant pipes before
starting the compressor.
R410A
Liquid pipe
Tightening
Pipe size O.D.
torque.
(mm)
(N·m)
ODø6.35 (1/4")
14 - 18
ODø6.35 (1/4")
14 - 18
Fig. 4-
4.. Positioning refrigerant and drain piping (Fig. 4-)
 PKFY-P·VHM-E
A Gas pipe
* Indicates the condition with accessories mounted.
B Liquid pipe
C Drain hose (Effective length: 400)
D Left-side piping knockout hole
E Right-side piping knockout hole
F Lower piping knockout hole
G Mount board 1
Flare nut O.D.
Gas pipe
Tightening
Liquid
Pipe size O.D.
torque.
pipe
(mm)
(N·m)
(mm)
ODø12.7 (1/2")
49 - 61
17
ODø12.7 (5/8")
49 - 61
17
Gas
pipe
(mm)
26