Item
V1
Upstream Valve Volume
V2
Downstream Valve Volume
D
Pipe Size NPT (in.)
L
Pipe Length (ft)
P
Valve Inlet Pressure (psig)
C
Burner Maximum Firing (cf/hr)
a
Divide inches w.c. by 27.7 to get psi.
b
Divide Btuh by 1000 to get cf/hr for natural gas or by 2550 to get cf/hr for LP gas.
Calculation of Valve Train Volume:
X = V1 + V2 + (A x L ÷ 144)
X = 0.0218 + 0.0267 + (3.356 x 1.75 ÷ 144) = 0.0893.
Calculation of Valve Proving Test Time:
Pipe Size NPT
(inches)
V4295
3/8
0.0002
1/2
0.0002
3/4
0.0008
1
0.0009
1-1/4
0.0045
1-1/2
0.0045
2
0.0089
2-1/2
0.0441
3
0.0441
4
Pipe Size NPT
(inches)
V4295
3/8
0.0011
1/2
0.0011
3/4
0.0026
1
0.0036
1-1/4
0.0148
1-1/2
0.0148
2
0.0267
2-1/2
0.0554
3
0.0554
4
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Table 12. VPS Worksheet Example.
Description
a
b
Table 13. V1 Upstream Volumes for Honeywell Valves.
V4297A1013
V4297A1005
0.0093
0.0090
0.0093
0.0090
0.0093
0.0090
0.0093
0.0093
Table 14. V2 Downstream Volumes for Honeywell Valves.
V4297A1013
V4297A1005
0.0282
0.0232
0.0282
0.0232
0.0282
0.0232
0.0282
0.0282
Information
Lookup Table
V5055
12
V4295
13
2 in. NPT
14
1.75 ft
2
2.5 mbtu
Test Time = 187,000 x (P x X ÷ C)
Test Time = 187,000 x (2 x 0.0893 ÷ 2500) = 13.4
seconds.
Round up to 14 seconds; enter 14 seconds into the VPS
Setup.
V48
0.0010
0.0046
0.0010
0.0046
0.0035
0.0046
0.0035
0.0218
0.0048
0.0218
0.0048
0.0227
0.0048
0.0227
0.0779
V48
0.0048
0.0067
0.0048
0.0067
0.0110
0.0067
0.0110
0.0238
0.0184
0.0238
0.0184
0.0245
0.0184
0.0245
0.0801
27
Results
0.0218
V1
0.0267
V2
3.356
A
1.75
L
2
P
2500
C
V5055
V5097A1004
0.0066
0.0066
0.0066
0.0066
0.0066
V5055
V5097A1004
0.0093
0.0093
0.0093
0.0093
0.0093
Formula Item
V5097A1012
0.0285
0.0285
0.0285
V5097A1012
0.0303
0.0303
0.0303
66-1162—2