Table 10. Blinking Fault Codes and Recommended Troubleshooting. (Continued)
Blink Code
System Failure
Code 5-3
Man-Open Switch, Start
*Man-Open
Switch or Control On in
Sw.; Start Sw.
the wrong operational
or Control On*
state.
Code 6-1
Relay Module self-test
*Internal Faults*
failure.
Code 6-2
Relay Module Self-Test
*Internal Faults*
failure.
Code 6-3
Fault with special OEM
*Device
input circuits.
Specific*
Code 6-4
VPS setup.
*Accessory
Fault*
Code 7-7
Unused at this time.
*Unused*
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
1. Check wiring and correct any errors.
2. Make sure that the Manual Open Valve Switch, Start Switch and Control are
operating properly.
3. Stat Switch held "On" too long.
4. Reset and sequence the relay module.
5. Reset and sequence the relay module. If the fault persists, replace the relay
module (RM7838A1014; RM7838B1013 or RM7838C1004 only).
1. Reset and sequence the relay module.
2. If fault reappears, remove power from the device, reapply power, then reset
and sequence the relay module.
3. If the fault persists, replace the relay module.
1. Reset and sequence the relay module.
2. If fault reappears, remove power from the device, reapply power, then reset
and sequence the relay module.
3. If fault does not repeat on the next cycle, check for electrical noise being
copied into the relay module through the external loads or possibly an
electrical grounding issue.
4. If the fault persists, replace the relay module.
1. Check wiring and operation of special OEM inputs.
2. Reset and sequence the relay module.
3. If fault reappears, remove power from the device, reapply power, then reset
and sequence the relay module.
4. If the fault does not repeat on the next cycle, check for electrical noise being
copied into the relay module through the external loads or possibly an
electrical grounding issue.
5. If the fault persists, replace the relay module.
1. Make sure Relay Module VP is programmed.
2. T6 and T17 powered at the same time—correct wiring.
3. Reset control if fault persists. Replace relay module.
Recommended Troubleshooting