YFF Series Indoor Units Outdoor Units FSF045 YFF045 REFRIGERANT R410A HEAT PUMP DECEMBER 2010 SM FSF045 1 -A. 0 GB...
Page 2
13-10 ......0 14-1 ......0 • Zero in this column indicates an original page. *Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual. SM FSF045 1-A.0 GB...
Easily accessible, and re-usable pre-filters (mesh) • Control The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming. For further details please refer to the Operation Manual, Appendix A. SM FSF045 1-A.0 GB...
Page 5
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Chapter 10. Inbox Documentation Each unit is supplied with its own installation and operation manuals. Matching Table INDOOR UNIT AWSI-FSF045-N13 OUTDOOR UNIT AWAU-YFF045-H13 √ SM FSF045 1-A.0 GB...
PRODUCT DATA SHEET PRODUCT DATA SHEET FSF045 / YFF045 R410A FSF045 Model Indoor Unit YFF 045 Model Outdoor Unit l l a i t s s t i n i l Btu/hr 42310 46400 Capacity 12.40 13.60 Power input 4.94 4.84...
C WB C DB Upper limit Cooling Lower limit C DB 15 C WB C DB Upper limit C DB C DB 18 C WB Heating Lower limit C DB C DB Voltage 360 – 440 V SM FSF045 1-A.0 GB...
Power Input, kW WB – Wet Bulb Temp., ( DB – Dry Bulb Temp., ( – Indoor OD – Outdoor (1) Marked area is below standard operating limits. For operating in low ambient conditions, Optional Accessories are needed. SM FSF045 1-A.0 GB...
Page 10
Capacity Correction Factor Due to Tubing Length Cooling TOTAL TUBING LENGTH Minimum recommended tubing length between indoor and outdoor units is 3m. Heating TOTAL TUBING LENGTH Minimum recommended tubing length between indoor and outdoor units is 3m. SM FSF045 1-A.0 GB...
Page 11
PERFORMANCE DATA & PRESSURE CURVES Pressure Curves: SAF024 / OU7-24 Z R410A 5.4.1 Cooling. SM FSF045 1-A.0 GB...
Page 12
PERFORMANCE DATA & PRESSURE CURVES 5.4.2 Heating. SM FSF045 1-A.0 GB...
Power Supply Wiring No. X 3 x 1.0 mm Cross Section mm (To IDU) Interconnecting Cable Model No. 5x1.0mm + 4x1.0mm X Cross Section mm Note: Power wiring cord should comply with local laws and electrical regulations requirementsl. SM FSF045 1-A.0 GB...
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required. SM FSF045 1-A.0 GB 10-1...
3. When 20 degree <RAT< 26 degree, upon initial startup, the unit will enter auto mode and run in automatic fan mode. If the other mode changes into auto mode, the previous running mode will remain. SM FSF045 1-A.0 GB 11-1...
When high pressure protection is detected for 3 seconds continuously, the high pressure switch is 4.2Mpa, the unit will stop and report the fault, it can not resume running automatically and display malfunction, it can resume by pressing ON/OFF. 11-2 SM FSF045 1-A.0 GB...
Page 21
Overheating protection in heating mode In heating mode, when it’s detected that the evaporator tube temperature (ICT) is too high, outdoor fan will stop running; when evaporator tube temperature resumes to normal range, outdoor fan will be started up. SM FSF045 1-A.0 GB 11-3...
Page 22
Press down button for 20 sec, the unit will force to cooling mode Function Select the function(vertical louver/horizontal louver/blow/E-heater/timer/air/sleep/turbo, etc), the function can be set or exit by up/down botton Speed Select the fan speed by pressing this button, the sequence is Auto, low, medium, high 11-4 SM FSF045 1-A.0 GB...
Confirmation of Power Supply Confirm that the power breaker operates(ON) normally; 12.1.2.2 Confirmation of Power Voltage Confirm that power voltage is AC380- 415V+/-10% for threee phase. If power voltage is not in this range, the unit may not operate normally. SM FSF045 1-A.0 GB 12-1...
Page 24
Three coil resistance is same. Check the resistance between three poles. The normal value should be 3 ohm@25℃. 12.2.5 Checking the Reverse Valve (RV). Running in heating mode, check the voltage between two pins of reverse valve connector, normal voltage is 220~240VAC. 12-2 SM FSF045 1-A.0 GB...
Page 25
EXPLODED VIEWS & SPARE PARTS LISTS EXPLODED VIEWS & SPARE PARTS LISTS 13.1 Indoor Unit: FSF045 SM FSF045 1-A.0 GB 13-1...
Need help?
Do you have a question about the FSF045 and is the answer not in the manual?
Questions and answers