Section 4. Gas Connections

Gas piping installation must be in accordance with the
latest edition of ANSI Z223.1 and all local codes. In
Canada, the installation must be in accordance with CAN/
CSA B149.1 and all local codes that apply.
The heater must be isolated from the gas supply piping
system by closing the individual manual shut off valve
during any pressure testing of the gas supply piping system
at test pressure greater than or equal to 1/2 psi (3.5kPa).
CAUTION
Permanent damage to the gas valve will occur if the installation
procedures are not followed correctly.
4.1

Supply Gas Requirements

3/4"
Model
NG
LP
JXi400
5 ft
20 ft
JXi260
15 ft
40 ft
JXi200
30 ft
70 ft
Numbers are for natural gas (0.60 Sp. Gr.) based on 1/2 inch (3.45 kPa) water column pressure drop. Check supply pressure with a
manometer, and local code requirements for variations.
Check supply pressure and local code requirements before proceeding with installation.
Consider pipe fi ttings when determining gas pipe sizing. For every elbow used add three (3) feet to straight pipe length.
Table shows the minimum supply gas pipe size required. Larger pipe size can be used if required by local code or if desired.
It is critical that the incoming gas supply pressure at the heater is within the maximum and minimum pressure requirements. If the range
of acceptable supply pressure is not provided, the gas supply system to the heater must be modifi ed to meet pressure requirements.
Table 2.
Supply Gas Pipe Size Requirements
Refer to
Table 2
for correct gas inlet piping length
from the gas meter to the heater.
Check the gas meter to make sure it will supply
enough gas to the heater and any other appliances
using the same gas supply. If unsure, contact your
local gas utility to confi rm.
Install a manual gas shutoff valve outside the heater
body for service and safety. Never install the shutoff
valve inside the body of the heater.
Install a sediment trap and union ahead of the gas
controls and outside the heater body. See
Do not use a restrictive gas cock.
ATTENTION
Do not use fl exible appliance connectors on any gas connections
unless the connector is CSA approved for outdoor installation, and is
marked with the BTUH capacity (which must be equal to or greater
than the heater rated input) and the type of gas (Natural or LP). Also,
any fl exible connectors, such as CSST buried underground must be
certifi ed for underground installation and meet all applicable codes.
Please note, use of fl exible connector still requires the installation of
a sediment trap per NFPA 54. See
|
Gas-Fired Pool & Spa Heater
Maximum Equivalent Pipe Length
Natural Gas at 1050 btu per cubic foot
Propane Gas at 2500 btu per cubic foot
1"
NG
LP
30 ft
60 ft
60 ft
150 ft
100 ft
240 ft
Figure 6.
Figure
6.
Installation & Operation Manual
The JXi pool and spa heaters are designed for use with either
natural gas or LP gas. Check the rating plate on the front of the
combustion chamber to be sure that the heater is designed to use
the type of gas being supplied. CONVERTING THIS HEATER FOR
USE WITH ANY OTHER FUEL TYPE IS NOT RECOMMENDED
BUT, WHEN NECESSARY, SHOULD ONLY BE PERFORMED BY A
LICENSED AND QUALIFIED PROFESSIONAL, AND ONLY AFTER
CONTACTING ZODIAC POOL SYSTEMS FOR THE PROPER
INSTRUCTIONS AND CONVERSION KIT.
All questions should be directed to the Zodiac customer service
center at 1-800-822-7933
1-1/4"
NG
LP
110 ft
260 ft
230 ft
230 ft
590 ft
490 ft
380 ft
600 ft
600 ft
NOTE: The gas line from the meter is usually larger than the
gas valve. Therefore, you will need to reduce connecting pipe as
necessary. Make this reduction as close to the heater as possible.
Figure 6.
Manual Shut-off Valve and Sediment Trap
ENGLISH
WARNING
1-1/2"
NG
LP
NG
560 ft
600 ft
600 ft
600 ft
PIPE
NIPPLE
SEDIMENT TRAP
Page 15
2"
LP
600 ft