Fault Record - Measurement Indication - Mitsubishi Electric melpto d series Operation Manual

Numerical protection relay
Table of Contents

Advertisement

A - 3
Fault record – measurement indication
This item can only be displayed when fault record data has been stored. The item data will not be shown when there is
no record data.
<< Example >>
(1)
First phenomena
(2)
Second phenomena
(3)
Third and more
Step
Description
1
The indication mode starts.
2
When this switch is kept depressed until
the item number "211" appears, the
A-phase current in the first phenomena
will be indicated.
Ex. : A-phase current: 0.9 kA
3
The B-phase current in the first
phenomena will be indicated.
Ex. : B-phase current: 0.9 kA.
4
The C-phase current in the first
phenomena will be indicated.
Ex. : C-phase current: 0 A
5
The zero-phase current in the first
phenomena will be indicated.
Ex. : Zero-phase current: 0 A
6
Changing the item number to "212" will
display the A-phase current in the second
phenomena.
Ex. : A-phase current: 0 A
7
The B-phase current in the second
phenomena will be indicated.
Ex. : B-phase current: 1.8 kA.
Where the following system fault currents have been recorded:
: A-phase = 0.9 kA, B-phase = 0.9 kA, C-phase = 0 A, Zero-phase = 0 A
: A-phase = 0 A, B-phase = 1.8 kA, C-phase = 1.8 kA, Zero-phase = 0 A
: No records
Switch
IND./IND.END
UP
UP
UP
UP
UP
UP
Operation
Press
Item No.
0
Once
Item No.
2
-
Item No.
2
Once
Item No.
2
Once
Item No.
2
Once
Item No.
2
Once
Item No.
2
Once
10
Indication
Item data
1
0
0.
0
kA
B-
C-
A-
phase
phase
phase
Item data
1
1
0.
kA
B-
C-
A-
phase
phase
phase
Item data
1
1
0.
kA
B-
C-
A-
phase
phase
phase
Item data
1
1
0.
0
kA
B-
C-
A-
phase
phase
phase
Item data
1
1
0.
0
kA
B-
C-
A-
phase
phase
phase
Item data
1
2
0.
0
kA
B-
C-
A-
phase
phase
phase
Item data
1
2
1.
kA
B-
C-
A-
phase
phase
phase
JEP0-IL9416
0
A
Zero-
phase
9
A
Zero-
phase
9
A
Zero-
phase
0
A
Zero-
phase
0
A
Zero-
phase
0
A
Zero-
phase
8
A
Zero-
phase