DRY OPERATION

Vane
setting notch
w8—9 Refer to page OC275-18.
w12
When room temperature is 64°F or below, the compressor cannot operate.
When room temperature rises over 64°F the compressor starts after a 3-minute time delay.
w13
Compressor ON time is decided by room temperature. Refer to page OC275-24.
w14
In dry operation, compressor ON makes the fan speed LOW. Also, when the compressor OFF and the pipe temperature
is 79°F or less, the fan stops, or when the compressor OFF and the pipe temperature is below 43°F the fan speed
changes to LOW mode.
It is not possible to set the fan speed with the remote controller
DRY
operation
NO
Initial dry
operation
YES
Vane initial setting
YES
Room temperature is
64°F or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
NO
Compressor &
thermostat ON
YES
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
OC275-19
w8
w12
NO
NO
w9
YES
NO
w14
YES
3-minute
time delay
NO
w9
Compressor &
thermostat
ON
NO
10-minute
NO
compressor
OFF
YES
w13
Compressor ON
time set
Compressor ON
w14
Fan speed LOW