Product Application; Construction; Rinciple Of Operation; Limitation Of Use - Sanitron S17A Owner's Manual

U ltraviolet water purifiers
Table of Contents

Advertisement

PRODUCT APPLICATION

C
ONSTRUCTION
The water purifi er is designed to mount horizontally.
The water purifi er's removable chamber head design allows for ease of maintenance. A drain port on the chamber
aids in draining of the purifi er.
The water purifi er's chamber and chamber head are passivated and electropolished type 316 Stainless Steel.
The ballast housing is a combination of Stainless Steel Type 304 and Aluminum Alloy.
Coated chambers are available for uses with special applications, consult Factory. Coated chambers are not recommended for
use in drinking water applications or in applications where the treated product is consumed.
The dual action wiper mechanism allows for quick and easy quartz sleeve cleaning, without interrupting service.
TM
Easy-off
end caps allow for quick and easy lamp change, without disconnecting from the water supply or draining the
purifi er. No tools are required.
P
O
RINCIPLE OF
PERATION
The SANITRON
®
design has been carefully conceived to provide adequate germicidal dosage throughout the disinfection
chamber. The dosage, as it applies to ultraviolet disinfection, is a function of time and the intensity of ultraviolet radiation to
which the water is exposed. The exposure time, in seconds, is the total time it takes the water to fl ow through the disinfection
chamber exposing it to the germicidal lamp. Exposure time is related to the fl ow rate; the higher the fl ow rate, the lower the
exposure time or the lower the fl ow rate, the higher the exposure time. The ultraviolet intensity is the amount of energy, per unit
time, emitted by the germicidal lamp. The dosage is the product of ultraviolet intensity and the exposure time. The operation of
the SANITRON
®
is as follows:
Water enters the purifi er and fl ows into the annular space between the quartz sleeve and the chamber wall.
Suspended microorganisms are exposed to the ultraviolet rays emitted by the germicidal lamp.
The translucent sight port, or optional ultraviolet monitor, provides visual indication of germicidal lamp operation.
The dual action wiper mechanism facilitates periodic cleaning of the quartz sleeve without disassembly or interruption of
purifi er operation.
Water leaving the purifi er is instantly ready for use, no further contact time is required.
L
U
IMITATION OF
SE
The water purifi er is intended for the use with visually clear water, not colored, cloudy or turbid. See "Water Quality" section
below. The water purifi er is NOT intended for the treatment of water that has an obvious contamination or intentional source,
such as raw sewage; nor is the unit intended to convert wastewater to microbiologically safe drinking water.
W
Q
ATER
UALITY
Water quality plays a major role in the transmission of germicidal ultraviolet rays. It is recommended that the water does not
exceed the following maximum concentration levels:
Effectively treating water with higher concentration levels than listed above can be accomplished, but may require added
measures to improve water quality to treatable levels. If, for any reason, it is believed the ultraviolet transmission is not
satisfactory, contact the factory.
4
Table 1 - Maximum Concentration Levels
Turbidity
Manganese
Total Suspended Solids
pH:
Color:
Hardness
Iron
Tannins:
UV Transmission
* Contact Factory for recommendations on applications where UV transmission is < 85%
< 1 NTU
0.05 mg/1
10 mg /1
6.5 - 9.5
None
6 GPG or 102.6 PPM
0.3 mg/1
< 0.1 ppm (0.1 mg/l)
>85% per cm*