Jumper Settings - Electra WNG 9 DCI INV Technical Manual

Multi split trio quattro dci
Table of Contents

Advertisement

CONTROL SYSTEM
Notes:
x For the temperature display, when a thermistor is shorted or disconnected it shows FLT
(FLt), when it is disabled it shows DIS (dis).
x It's possible to present a number between 999 and 99,999 by alternating between two
numbers (each number is presented for 1 second). The two numbers format is "xx, yyy".
x Pressing select + escape together for 5 seconds will reset the counter to 0.
x The compressor time is measured in hours.
11.9

Jumper settings

11.9.1
Jumper definitions
0 = open (disconnected)
1 = closed (shorted)
11.9.2
OFAN Jumpers
OFAN use parameters
Panasonic- EHD80
Nidec SIC-71FW-F170-1
Shinano
EEPROM
11.9.3
Compressor Jumpers
Compressor use parameters
TNB220FLBM (ROM)
EEPROM
11.10
System Parameters
11.10.1
General parameters
Parameter
ODUCodeL
imit
11.10.2
Protection Parameters
Deicer Parameters
Parameter
DST
DSTF
DIF (min)
CTMR (min)
TimeD (min)
DIT (min)
DTmin (min)
DImin (min)
DImax (min)
DeicSPChRV
EEVDeicerOpen
DEICT1 (sec)
DEICT2 (sec)
DEICT3 (sec)
OptimDeicSP
11-24
J2
J1
0
0
0
1
1
0
1
1
J3
0
1
Default Value
6
Default
8
12
30
15
1
10
3
30
120
0
180
50
36
6
90
Revision 0