Chapter 8 RAS Information
(d) Error event
Value
0
3
9
17
18
50-53
54
55
56
57
8
58
59
60
61
62
202
212
213
Others Unprescribed error
(e) Bus error counter
Severe bus error counter
34
7
6
5
Error Event
Remote node operating normally
Remote node internal function
invalid
No response for data
No response from slave
Master not participating in token
ring
Internal error
No master parameter
Master parameter error
No remote node parameter
No remote node parameter
Duplicate remote node address
Transmit address out of range
Receive address out of range
Duplicate receive area
Duplicate transmit area
Insufficient space
Setup data read error
System error
F
E
D
C
B
4
3
2
1
Err_Event
Table 8-9 Error events
Cause
Remote
Check the setting and use correct GSD
file
Remote
Re-examine bus cable
Remote
Re-examine bus cable andre-examine
remote node address
Master
Re-examine master node address
Master
Contact Toshiba
Master
Download setup information again
System
Contact Toshiba
design
System
Download setup information again
design
System
Contact Toshiba
design
System
Re-examine remote node address
design
System
Re-examine transmit address
design
System
Re-examine receive address
design
System
Re-examine receive address
design
System
Re-examine transmit address
design
Master
Contact Toshiba
Master
Download setup information once more
Master
Contact Toshiba
-
Contact Toshiba
Table 8-10 Bus error counter
A
9
8
7
6
Bus_Error_count
model 2000 PROFIBUS Module User's Manual for S2T/S2E
0
Action
5
4
3
2
1
0