Status LED
RDY (green)
RUN (green)
TOKEN
(green)
ERR (red)
ACC(green)
Configurator port (CONFIG)
PC (PROFIBUS-DP configurator) connector.
Transmission cable terminating resistor specification switch (TERM)
TERM (terminating resistor)
nodes on both ends.
Transmission cable connector (PROFIBUS-DP)
PROFIBUS-DP transmission cable connector
Reset switch (RESET)
Press when the PF611 is abnormal or when initializing the PF611 independent of the
controller.
6F8C1147
2.4 Name of PF611 Module Components and Parts
Table 2-2 Status LED
ON
Transmission module normal
Cyclic flash
Firmware not stored.
(1 Hz)
Cyclic flash
Hardware error or system error or in
(4 Hz)
downloading firmware configuration data
OFF
Hardware failure
ON
Communicating
Cyclic flash
Standby
(4 Hz)
Acyclic flash
Configuration error or fatal error
ON
Token retained
OFF
No token
ON
Error on communication line
OFF
No error detected
ON
Controller accessing
OFF
Controller not accessing
ON: Terminated with terminating resistor. Turn on at
2
7