Repairs
(cont.)
Checking the outlet temperature sensor (gas condensing combi
boiler)
A
20
10
8
6
4
2
1
0.8
0.6
0.4
10 30 50 70 90 110
Temperature in °C
1. Pull leads from outlet temperature
sensor A.
2. Check the sensor resistance and
compare it with the curve.
3. In the event of severe deviation
replace the sensor.
Note
Water can leak when replacing the
outlet temperature sensor. Shut off
the cold water supply. Drain the DHW
line and the plate heat exchanger (on
the DHW side).